Key Commercial Data
Orderkey | 1052649 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
GTIN | 4055626676746 |
Weight per Piece (excluding packing) | 35.860 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 6000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 … 500 Hz / 2.5 h / X, Y, Z) |
General
IEC test classification | II |
---|---|
T2 | |
EN type | T2 |
Mode of protection | (DC+/DC-) – PE |
Mounting type | on base element |
Color | light grey RAL 7035 |
Housing material | PA 6.6-FR 20% GF |
PBT-FR | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | Male |
Number of positions | 1 |
Surge protection fault message | optical |
Additional descriptions
Note | The VAL-SEC-T2-GDT-800DC-P protective plug (order No.: 1052649) is only to be used in series connection with a VAL-SEC-T2-220DC-P (order No.: 2907879) or VAL-SEC-T2- 380DC-P (order No.: 2907880). It is not designed for direct use on mains voltage. |
---|---|
Uagn ≥ 600 V |
Protective circuit
Residual current IPE | ≤ 5 µA |
---|---|
Nominal discharge current In(8/20) µs | 20 kA |
Maximum discharge current Imax(8/20) µs | 40 kA |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 0.5 kV (at In) |
≤ 0.5 kV (at 10 kA) | |
≤ 0.5 kV (at 5 kA) | |
≤ 0.5 kV (at 4 kA) | |
≤ 0.5 kV (at 2 kA) | |
Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
Response time tA | ≤ 100 ns |