Key Commercial Data
Orderkey | 2906281 |
---|---|
Packing unit | 12 pc |
Minimum order quantity | 12 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 39 (C-4-2017) |
GTIN | 4055626063065 |
Weight per Piece (excluding packing) | 149.000 g |
Custom tariff number | 85363090 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 (only when all terminal points are used) |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | max. 2000 m |
Permissible humidity (operation) | 5 % … 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 … 500 Hz / 2.5 h / X, Y, Z) |
General
IEC test classification | I / II |
---|---|
T1 / T2 | |
I | |
EN type | T1 / T2 |
IEC power supply system | DC |
Mode of protection | L-PEN |
(L+) – (L-) | |
(L-) – PE | |
(L+) – PE | |
Mounting type | DIN rail: 35 mm |
Color | black |
Housing material | PBT |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 1 |
Surge protection fault message | Optical, remote indicator contact |
Protective circuit
Nominal voltage UN | -48 V DC (RRH) |
---|---|
60 V DC | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 75 V AC |
100 V DC | |
Maximum continuous operating voltage UC(L-PEN) | 75 V AC |
100 V DC | |
75 V AC | |
100 V DC | |
Rated load current IL | 80 A |
80 A | |
Residual current IPE | ≤ 0.6 mA |
≤ 0.6 mA | |
Standby power consumption PC | ≤ 45 mVA |
≤ 45 mVA | |
Nominal discharge current In(8/20) µs | 12.5 kA |
Maximum discharge current Imax(8/20) µs | 30 kA |
30 kA | |
Maximum discharge current Imax(8/20) µs (L-N) | 30 kA |
Maximum discharge current Imax(8/20) µs (L-PEN) | 30 kA |
Impulse discharge current (10/350) µs, charge | 6.25 As |
Impulse discharge current (10/350) µs, specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 12.5 kA |
12.5 kA | |
Impulse discharge current (10/350) µs (L-N), charge | 6.25 As |
6.25 As | |
Impulse discharge current (10/350) µs (L-N), specific energy | 39 kJ/Ω |
39 kJ/Ω | |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 12.5 kA |
12.5 kA | |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up | ≤ 0.4 kV |
Voltage protection level Up(L-N) | ≤ 0.4 kV |
Voltage protection level Up(L-PEN) | ≤ 0.4 kV |
Residual voltage Ures | ≤ 0.4 kV (at In) |
≤ 0.35 kV (at 10 kA) | |
≤ 0.3 kV (at 5 kA) | |
≤ 0.275 kV (at 4 kA) | |
≤ 0.25 kV (at 3 kA) | |
TOV behavior at UT | 100 V AC (5 s / withstand mode) |
130 V DC (5 s / withstand mode) | |
Response time tA | ≤ 25 ns |
Response time tA(L-N) | ≤ 25 ns |
Response time tA(L-PEN) | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 80 A AC (gG – 16 mm²) |
80 A AC (gG – 16 mm²) | |
Max. backup fuse with branch wiring | 160 A AC (gG) |
160 A AC (gG) |
Connection data
Connection method | Screw connection |
---|---|
Screw thread | M5 |
Tightening torque | 4.5 Nm |
30 lbf-in. (UL) | |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² … 25 mm² |
Conductor cross section solid | 1.5 mm² … 35 mm² |
Conductor cross section AWG | 15 … 2 |
10 … 2 (UL) |