Key Commercial Data
Orderkey | 2859505 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 41 (C-6-2013) |
GTIN | 4017918981464 |
Weight per Piece (excluding packing) | 310.500 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 … 500 Hz / 2.5 h / X, Y, Z) |
General
IEC test classification | II |
---|---|
T2 | |
EN type | T2 |
IEC power supply system | TN-S |
TT | |
Mode of protection | L-N |
L-PE | |
N-PE | |
Mounting type | DIN rail: 35 mm |
Color | gray/blue |
black | |
Housing material | PBT-FR |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 3 |
Surge protection fault message | Optical, remote indicator contact |
Protective circuit
Nominal voltage UN | 240/415 V AC (TN-S) |
---|---|
240/415 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC(L-N) | 350 V AC |
Maximum continuous operating voltage UC(L-PE) | 350 V AC |
Maximum continuous voltage UC(N-PE) | 264 V AC |
Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
63 A (TWIN ferrule 2 x 10 mm²) | |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In(8/20) µs (L-N) | 20 kA |
Nominal discharge current In(8/20) µs (N-PE) | 20 kA |
Maximum discharge current Imax(8/20) µs (L-N) | 40 kA |
Maximum discharge current Imax(8/20) µs (N-PE) | 40 kA |
Follow current interrupt rating Ifi(N-PE) | 100 A (264 V AC) |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up(L-N) | ≤ 1.5 kV |
Voltage protection level Up(L-PE) | ≤ 1.9 kV |
Voltage protection level Up(N-PE) | ≤ 1.5 kV |
Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
≤ 1.3 kV (at 10 kA) | |
≤ 1.2 kV (at 5 kA) | |
≤ 1.1 kV (at 4 kA) | |
≤ 1 kV (at 2 kA) | |
Residual voltage Ures(N-PE) | ≤ 0.5 kV (at In) |
≤ 0.5 kV (at 10 kA) | |
≤ 0.5 kV (at 5 kA) | |
≤ 0.5 kV (at 4 kA) | |
≤ 0.5 kV (at 2 kA) | |
TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
440 V AC (120 min / safe failure mode) | |
TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA(L-N) | ≤ 25 ns |
Response time tA(N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
63 A (gG / TWIN ferrule 2x 10mm²) | |
Max. backup fuse with branch wiring | 315 A (gG) |
Indicator/remote signaling
Switching function | PDT contact |
---|---|
Operating voltage | 5 V AC … 250 V AC |
125 V DC (200 mA DC) | |
Operating current | 5 mA AC … 1 A AC |
1 A DC (30 V DC) | |
Connection method | Pluggable screw connection |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² … 1.5 mm² |
Conductor cross section solid | 0.14 mm² … 1.5 mm² |
Conductor cross section AWG | 28 … 16 |