Key Commercial Data
Orderkey | 3046799 |
---|---|
Packing unit | 50 pc |
Minimum order quantity | 50 pc |
Note | Made to Order (non-returnable) |
GTIN | 4046356140218 |
Weight per Piece (excluding packing) | 13.300 g |
Custom tariff number | 85369010 |
Country of origin | DE (Germany) |
General
Number of positions | 1 |
---|---|
Number of levels | 1 |
Number of connections | 2 |
Nominal cross section | 4 mm² |
Color | orange |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 1.02 W |
Maximum load current | 20 A (with 6 mm² conductor cross section) |
20 A (with 6 mm² conductor cross section) | |
Nominal current IN | 20 A (with 4 mm² conductor cross section) |
Nominal voltage UN | 500 V |
Open side panel | No |
Shock protection test specification | IEC 60529:2001-02 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 7.3 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 0.14 mm² / 0.2 kg |
4 mm² / 0.9 kg | |
6 mm2/ 1.4 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.14 mm² |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Conductor cross section tensile test | 6 mm² |
Tractive force setpoint | 80 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 6,4 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 0.48 kA |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 1, class B, body mounted |
Test frequency | f1= 5 Hz to f2= 150 Hz |
ASD level | 1.857 (m/s2)2/Hz |
Acceleration | 0,8 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 5 g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Connection data
Connection method | Screw connection |
---|---|
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section solid min. | 0.14 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 10 |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 6 mm² |
Min. AWG conductor cross section, flexible | 26 |
Max. AWG conductor cross section, flexible | 10 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
2 conductors with same cross section, solid min. | 0.14 mm² |
2 conductors with same cross section, solid max. | 1.5 mm² |
2 conductors with same cross section, stranded min. | 0.14 mm² |
2 conductors with same cross section, stranded max. | 1.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 2.5 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.14 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 1.5 mm² |
Stripping length | 9 mm |
Internal cylindrical gage | A4 |
Screw thread | M3 |
Tightening torque, min | 0.6 Nm |
Tightening torque max | 0.8 Nm |
Standards and Regulations
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-1 | |
Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |