Key Commercial Data
Orderkey | 3044173 |
---|---|
Packing unit | 50 pc |
Catalog page | Page 251 (C-1-2017) |
GTIN | 4017918960452 |
Weight per Piece (excluding packing) | 29.120 g |
Custom tariff number | 85369010 |
Country of origin | DE (Germany) |
General
Number of levels | 1 |
---|---|
Number of connections | 2 |
Nominal cross section | 10 mm² |
Color | green-yellow |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Area of application | Railway industry |
Machine building | |
Plant engineering | |
Process industry | |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Open side panel | Yes |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 1, class B, body mounted |
Test frequency | f1= 5 Hz to f2= 150 Hz |
ASD level | 1.857 (m/s2)2/Hz |
Acceleration | 0,8 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 5 g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Dimensions
Width | 10.2 mm |
---|---|
End cover width | 2.2 mm |
Length | 47.7 mm |
Height | 46.9 mm |
Height NS 35/7,5 | 47.5 mm |
Height NS 35/15 | 55 mm |
Connection data
Note | Please observe the current carrying capacity of the DIN rails. |
---|---|
Connection method | Screw connection |
Screw thread | M4 |
Stripping length | 10 mm |
Tightening torque, min | 1.5 Nm |
Tightening torque max | 1.8 Nm |
Connection in acc. with standard | IEC 60947-7-2 |
Note | Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 16 mm² |
Min. AWG conductor cross section, flexible | 20 |
Max. AWG conductor cross section, flexible | 6 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 10 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 10 mm² |
2 conductors with same cross section, solid min. | 0.5 mm² |
2 conductors with same cross section, solid max. | 4 mm² |
2 conductors with same cross section, stranded min. | 0.5 mm² |
2 conductors with same cross section, stranded max. | 4 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 6 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 2.5 mm² |
Connection in acc. with standard | IEC/EN 60079-7 |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Internal cylindrical gage | A6 |
Standards and Regulations
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-2 | |
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |