Key Commercial Data
Orderkey | 2774091 |
---|---|
Packing unit | 50 pc |
Catalog page | Page 435 (C-1-2017) |
GTIN | 4017918068318 |
Weight per Piece (excluding packing) | 14.350 g |
Custom tariff number | 85369010 |
Country of origin | PL (Poland) |
General
Number of levels | 2 |
---|---|
Number of connections | 4 |
Nominal cross section | 4 mm² |
Color | blue |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 1.02 W (the value is multiplied when connecting multiple levels) |
Connection in acc. with standard | IEC 60947-7-1 |
Nominal current IN | 32 A |
Maximum load current | 32 A (with 4 mm² conductor cross section) |
Nominal voltage UN | 500 V |
Open side panel | Yes |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 7.3 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Checking the mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 0.2 mm² / 0.2 kg |
4 mm² / 0.9 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.2 mm² |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 32/NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 3.2 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 0.48 kA |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Relative insulation material temperature index (Elec.; UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Dimensions
Width | 6.2 mm |
---|---|
Length | 56 mm |
Height NS 35/7,5 | 62 mm |
Height NS 35/15 | 69.5 mm |
Height NS 32 | 67 mm |
Connection data
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
Cross section with insertion bridge, solid max. | 4 mm² |
Cross section with insertion bridge, stranded max. | 2.5 mm² |
2 conductors with same cross section, solid min. | 0.2 mm² |
2 conductors with same cross section, solid max. | 1.5 mm² |
2 conductors with same cross section, stranded min. | 0.2 mm² |
2 conductors with same cross section, stranded max. | 1.5 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.25 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 1.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 1.5 mm² |
Cross section with insertion bridge, solid max. | 4 mm² |
Cross section with insertion bridge, stranded max. | 2.5 mm² |
Stripping length | 8 mm |
Screw thread | M3 |
Tightening torque, min | 0.6 Nm |
Tightening torque max | 0.8 Nm |
Standards and Regulations
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-1 | |
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |