Key Commercial Data
Orderkey | 3061473 |
---|---|
Packing unit | 5 pc |
Minimum order quantity | 5 pc |
Note | Made to Order (non-returnable) |
GTIN | 4046356578714 |
Weight per Piece (excluding packing) | 397.220 g |
Custom tariff number | 85369010 |
Country of origin | IN (India) |
General
Number of levels | 1 |
---|---|
Number of connections | 2 |
Potentials | 1 |
Color | gray |
Insulating material | PA-F |
Flammability rating according to UL 94 | HB |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | II |
Maximum load current | 415 A (with 240 mm² conductor cross section) |
Nominal current IN | 415 A |
Nominal voltage UN | 1000 V |
Open side panel | No |
Connection data
Connection method | Bolt connection |
---|---|
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section solid min. | 70 mm² |
Conductor cross section solid max. | 240 mm² |
Conductor cross section flexible min. | 70 mm² |
Conductor cross section flexible max. | 240 mm² |
Min. AWG conductor cross section, flexible | 2/0 |
Max. AWG conductor cross section, flexible | 500 kcmil |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 70 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 180 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 70 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 185 mm² |
2 conductors with same cross section, solid min. | 35 mm² |
2 conductors with same cross section, solid max. | 95 mm² |
2 conductors with same cross section, stranded min. | 50 mm² |
2 conductors with same cross section, stranded max. | 95 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 35 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 50 mm² |
Cable lug connection according to standard | DIN 46234 |
Min. cross section for cable lug connection | 25 mm² |
Max. cross section for cable lug connection | 240 mm² |
Hole diameter, min. | 17 mm |
Bolt diameter | 16 mm |
Screw thread | M16 |
Tightening torque, min | 30 Nm |
Tightening torque max | 35 Nm |
Cable lug connection according to standard | DIN 46235 |
Min. cross section for cable lug connection | 50 mm² |
Max. cross section for cable lug connection | 185 mm² |
Hole diameter, min. | 17 mm |
Bolt diameter | 16 mm |
Screw thread | M16 |
Tightening torque, min | 30 Nm |
Tightening torque max | 35 Nm |
Cable lug connection according to standard | DIN 46237 |
Min. cross section for cable lug connection | 25 mm² |
Max. cross section for cable lug connection | 240 mm² |
Hole diameter, min. | 11 mm |
Bolt diameter | 10 mm |
Screw thread | M10 |
Tightening torque, min | 30 Nm |
Tightening torque max | 35 Nm |
Stripping length | 34 mm |
Tightening torque, min | 25 Nm |
Tightening torque max | 30 Nm |
Power rail | 40 mm x 5 mm |
Standards and Regulations
Connection in acc. with standard | UL |
---|---|
IEC 60947-7-1 | |
Flammability rating according to UL 94 | HB |
Environmental Product Compliance
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |