Key Commercial Data
| Orderkey | 2858182 |
|---|---|
| Packing unit | 25 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 105 (TT-2009) |
| GTIN | 4017918877897 |
| Weight per Piece (excluding packing) | 22.650 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | IEC 60664-1 |
| VDE 0110-1 | |
| Mounting type | DIN rail: 35 mm |
| Type | Double-level terminal block with PE foot |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C3 |
|---|---|
| VDE requirement class | C3 |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 32 A (≤ 60 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 119 A |
| Total discharge current Itotal(8/20) µs | 119 A |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 119 A |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 119 A |
| Nominal pulse current Ian (10/1000) µs (line-line) | 23 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 23 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 60 V |
| Residual voltage at In(line-line) | ≤ 80 V |
| Residual voltage at In(line-earth) | ≤ 80 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 65 V |
| Voltage protection level Up(line-line) | 55 V (C3 – 10 A) |
| Voltage protection level Up(line-earth) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.1 dB (≤ 400 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 2 MHz |
| Capacity (line-earth) | 1.1 nF (with 1 MHz) |
| Surge protection fault message | none |
| Impulse durability (line-line) | C3 – 10 A |
| Impulse durability (line-earth) | C3 – 10 A |
Connection data
| Connection method | Spring-cage connection |
|---|---|
| Connection method IN | Spring-cage |
| Connection method OUT | Spring-cage |
| Conductor cross section flexible | 0.5 mm² … 4 mm² |
| Conductor cross section solid | 0.5 mm² … 6 mm² |
| Conductor cross section AWG | 20 … 10 |