Key Commercial Data
Orderkey | 2858904 |
---|---|
Packing unit | 10 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 96 (C-6-2015) |
GTIN | 4017918938024 |
Weight per Piece (excluding packing) | 28.830 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -40 °C … 85 °C |
---|---|
Altitude | max. 2000 m |
Degree of protection | IP20 |
General
Housing material | PA 6.6 |
---|---|
Flammability rating according to UL 94 | V-2 |
Color | black |
Standards for cearances and creepage distances | EN 60664-1 |
IEC 60664-1 | |
Overvoltage category | III |
Degree of pollution | 2 |
Mounting type | DIN rail: 35 mm |
Type | Double-level terminal block with disconnect knife |
Number of positions | 2 |
Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
VDE requirement class | C1 |
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 30 V DC |
21 V AC | |
Rated current | 350 mA (45°C) |
Operating effective current ICat UC | ≤ 10 µA |
Standby power consumption PC | ≤ 1.78 VA |
Residual current IPE | ≤ 2 µA |
Nominal discharge current In(8/20) µs (line-line) | 5 kA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Pulse discharge current Iimp(10/350) µs | 1 kA (per path) |
Total discharge current Itotal(8/20) µs | 10 kA |
Total discharge current Itotal(10/350) µs | 2 kA |
Max. discharge current Imax(8/20) µs maximum (line-line) | 5 kA |
Max. discharge current Imax(8/20) µs maximum (line-earth) | 5 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 100 A |
Nominal pulse current Ian (10/1000) µs (line-earth) | 200 A (in total) |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 40 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 600 V |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 40 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 600 V |
Residual voltage at In(line-line) | ≤ 40 V |
Voltage protection level Up(line-line) | ≤ 60 V (C2 – 10 kV / 5 kA) |
≤ 40 V (stat.) | |
Voltage protection level Up(line-earth) | ≤ 600 V (C2 – 10 kV / 5 kA) |
Response time tA(line-line) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 1 dB (400 kHz/50 Ω) |
typ. 0.4 dB (150 kHz/150 Ω) | |
typ. 0.1 dB (30 kHz/600 Ω) | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 3 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1 MHz |
Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 250 kHz |
Capacity (line-line) | 4 nF |
Capacity (line-earth) | 2 pF |
Resistance in series | 6.6 Ω ±10 % |
Surge protection fault message | none |
Max. required back-up fuse | 370 mA |
Impulse durability (line-line) | C2 – 10 kV/5 kA |
C3 – 100 A | |
Impulse durability (line-earth) | C2 – 10 kV/5 kA |
D1 – 1 kA | |
C3 – 100 A |
Connection data
Connection method | Spring-cage connection |
---|---|
Connection method IN | Spring-cage |
Connection method OUT | Spring-cage |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section solid | 0.2 mm² … 4 mm² |
Conductor cross section AWG | 24 … 14 |