Key Commercial Data
Orderkey | 2801458 |
---|---|
Packing unit | 10 pc |
Catalog page | Page 97 (C-6-2015) |
GTIN | 4046356769204 |
Weight per Piece (excluding packing) | 26.260 g |
Custom tariff number | 85365019 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -40 °C … 80 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Altitude | ≤ 2000 m |
Degree of protection | IP20 |
General
Housing material | PA 6.6 |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | black |
Standards for cearances and creepage distances | IEC 60664-1 |
Mounting type | DIN rail: 35 mm |
Type | Double-level terminal block |
Number of positions | 2 |
Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
VDE requirement class | C1 |
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 30 V DC |
21 V AC | |
Rated current | 6 A (40 °C) |
Operating effective current ICat UC | ≤ 1 µA |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In(8/20) µs (line-line) | 300 A |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Pulse discharge current Iimp(10/350) µs | 500 A (per path) |
Total discharge current Itotal(8/20) µs | 5 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 25 A |
Nominal pulse current Ian (10/1000) µs (line-earth) | 50 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 45 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 800 V |
Output voltage limitation at (8/20) µs (line-line) | ≤ 50 V (at 300 A) |
Output voltage limitation at (8/20) µs (line-earth) | ≤ 750 V (at 500 A) |
≤ 1.25 kV (at 5 kA) | |
Residual voltage at In(line-line) | ≤ 50 V (at 300 A) |
Residual voltage at In(line-earth) | ≤ 750 V (at 500 A) |
≤ 1.25 kV (at 5 kA) | |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 45 V (at 25 A) |
Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 1.1 kV (at 50 A) |
Voltage protection level Up(line-line) | ≤ 50 V (C1 – 0,6 kV / 300 A) |
≤ 45 V (C3 – 25 A) | |
≤ 45 V (1 kV/μs) | |
Voltage protection level Up(line-earth) | ≤ 1.25 kV (C2 – 10 kV / 5 kA) |
≤ 1.1 kV (C3 – 50 A) | |
≤ 750 V (C1 – 1 kV/500 A) | |
≤ 800 V (1 kV/μs) | |
Response time tA(line-line) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.3 dB (330 kHz/150 Ω) |
typ. 0.3 dB (1.1 kHz / 50 Ω) | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 3.3 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1 MHz |
Capacity (line-line) | ≤ 2 nF |
Surge protection fault message | none |
Max. required back-up fuse | 6.3 A (T/IEC 60127-2/3) |
Impulse durability (line-line) | C1 – 0.6 kV / 300 A |
C3 – 25 A | |
Impulse durability (line-earth) | C2 – 10 kV/5 kA |
D1 – 500 A | |
C1 – 1 kV/500 A | |
C3 – 50 A | |
Pulse reset time (line-earth) | ≤ 700 ms, at Ucand 10 A |
Overload failure mode (line-line) | Mode 2 |
Connection data
Connection method | Spring-cage connection |
---|---|
Connection method IN | Spring-cage |
Connection method OUT | Spring-cage |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section solid | 0.2 mm² … 4 mm² |
Conductor cross section AWG | 24 … 12 |