General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-2 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | DIN rail: 35 mm |
| Type | Single-level terminal block – separate PE connection |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C3 |
|---|---|
| VDE requirement class | C3 |
| Nominal voltage UN | 24 V AC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 32 A (50 °C) |
| Operating effective current IC at UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In (8/20) µs (line-earth) | 119 A |
| Total discharge current Itotal (8/20) µs | 119 A |
| Max. discharge current Imax (8/20) µs maximum (line-earth) | 119 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 23.2 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 62 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 58 V |
| Residual voltage at In (line-earth) | ≤ 84 V |
| Response time tA (line-earth) | ≤ 1 ns |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 1.6 MHz |
| Capacity (line-earth) | 1.03 nF |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C3 – 10 A |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² … 4 mm² |
| Conductor cross section solid | 0.2 mm² … 4 mm² |
| Conductor cross section AWG | 24 … 12 |