Key Commercial Data
Orderkey | 2903154 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 223 (C-4-2017) |
GTIN | 4046356960953 |
Weight per Piece (excluding packing) | 1,175.500 g |
Custom tariff number | 85044030 |
Country of origin | CN (China) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
Nominal input voltage range | 3x 400 V AC … 500 V AC |
---|---|
2x 400 V AC … 500 V AC | |
Input voltage range | 3x 400 V AC … 500 V AC -20 % ….+15 % |
2x 400 V AC … 500 V AC -10 % … +15 % | |
AC frequency range | 50 Hz … 60 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 3x 0.6 A (400 V AC) |
3x 0.6 A (500 V AC) | |
2x 1.1 A (400 V AC) | |
2x 1.1 A (500 V AC) | |
Nominal power consumption | 451.7 VA |
Inrush surge current | ≤ 26 A (typical) |
Mains buffering | typ. 10 ms (400 V AC) |
typ. 20 ms (500 V AC) | |
Input fuse | 3.15 A (internal (device protection), slow-blow) |
Choice of suitable circuit breakers | 6 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.58 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 24 V DC … 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A |
Dynamic Boost (IDyn.Boost) | 15 A (5 s) |
Derating | > 60 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Output overvoltage protection | ≤ 30 V DC |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 3 % (Dynamic load change 10 % … 90 %, 10 Hz) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | ≤ 20 mVPP |
Output power | 240 W |
Typical response time | < 1 s |
Maximum power dissipation in no-load condition | < 1.1 W (400 V AC) |
Power loss nominal load max. | < 22 W (480 V AC) |
General
Net weight | 0.9 kg |
---|---|
Efficiency | > 92 % (at 400 V AC and nominal values) |
Insulation voltage input/output | 3 kV AC (type test) |
1.5 kV AC (routine test) | |
Protection class | I (in closed control cabinet) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 2100000 h (25 °C) |
> 1200000 h (40 °C) | |
> 590000 h (60 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |