Key Commercial Data
Orderkey | 2868538 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 244 (C-4-2017) |
GTIN | 4046356519960 |
Weight per Piece (excluding packing) | 75.000 g |
Custom tariff number | 85044030 |
Country of origin | PL (Poland) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Input data
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
Input voltage range | 85 V AC … 264 V AC |
95 V DC … 250 V DC | |
AC frequency range | 45 Hz … 65 Hz |
Frequency range DC | 0 Hz |
Current consumption | 0.26 A (120 V AC) |
0.13 A (230 V AC) | |
Nominal power consumption | 38.7 VA |
Inrush surge current | < 15 A (typical) |
Mains buffering | typ. 15 ms (120 V AC) |
typ. 90 ms (230 V AC) | |
Input fuse | 1.25 A (slow-blow, internal) |
Choice of suitable circuit breakers | 6 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.38 |
Output data
Nominal output voltage | 12 V DC ±1 % |
---|---|
Nominal output current (IN) | 1 A (-25 °C … 55 °C) |
1.1 A (-25°C … 40°C permanent ) | |
Output current Imax | 1.8 A |
Derating | 55 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | max. 25 V DC |
Output overvoltage protection | < 25 V DC |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 20 mVPP(20 MHz) |
Output power | 12 W |
Typical response time | < 0.5 s |
Peak switching voltages nominal load | < 10 mVPP(20 MHz) |
Maximum power dissipation in no-load condition | < 0.4 W |
Power loss nominal load max. | < 2.8 W |
General
Net weight | 0.07 kg |
---|---|
Efficiency | > 83 % (for 230 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
3.75 kV AC (routine test) | |
Insulation voltage input / PE | 3.5 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage output / PE | 500 V DC (routine test) |
Protection class | II (in closed control cabinet) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | |
> 1478000 h (40 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |