Key Commercial Data
Orderkey | 2905417 |
---|---|
Packing unit | 10 pc |
Catalog page | Page 448 (C-5-2017) |
GTIN | 4017918079406 |
Weight per Piece (excluding packing) | 58.800 g |
Custom tariff number | 85364190 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | 0 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | 0 °C … 70 °C |
Input data
Nominal input voltage UN | 24 V DC |
---|---|
Input voltage range in reference to UN | 0.9 … 1.1 |
Input voltage range | 21.6 V DC … 26.4 V DC |
Switching threshold “0” signal in reference to UN | ≤ 0.4 |
Switching threshold “1” signal in reference to UN | ≥ 0.8 |
Typical input current at UN | 7 mA |
Operating voltage display | Yellow LED |
Type of protection | Reverse polarity protection |
RC element | |
Protective circuit/component | RC element |
Transmission frequency | 10 Hz |
Power dissipation for nominal condition | 0.17 W |
Output data
Output nominal voltage | 400 V AC |
---|---|
Output voltage range | 24 V AC … 420 V AC |
Limiting continuous current | 3 A (see derating curve) |
Maximum inrush current | 125 A (t = 10 ms) |
Min. load current | 50 mA |
Leakage current | approx. 12 mA |
Surge current | 125 A (t = 10 ms) |
Peak offstate voltage | 800 V (Periodic peak reverse voltage) |
Voltage drop at max. limiting continuous current | ≤ 1.2 V |
Type of protection | Surge protection |
RC element | |
Protective circuit/component | Varistor |
RC element |
General
Test voltage input/output | 2.5 kV AC |
---|---|
2.5 kV AC | |
Mounting position | Horizontal DIN rail |
Standards/regulations | IEC 60664 |
EN 50178 | |
Degree of pollution | 2 |
Overvoltage category | III |