Key Commercial Data
Orderkey | 3969928 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 614 (C-1-2017) |
GTIN | 4055626127712 |
Weight per Piece (excluding packing) | 570.300 g |
Custom tariff number | 85366990 |
Country of origin | PL (Poland) |
General
Number of positions | 14 |
---|---|
Number of levels | 1 |
Number of connections | 28 |
Potentials | 14 |
Nominal cross section | 6 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 4 kV |
Test surge voltage | 5 kV |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 1.31 W |
Ambient temperature (operation) | -60 °C … 100 °C |
Maximum load current | 30 A (with 10 mm² conductor cross section) |
Current Ith | 24 A |
Nominal voltage UN | 400 V AC/DC |
Open side panel | No |
Terminal block mounting | 0.8 Nm … 1 Nm |
Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection | guaranteed |
Note regarding shock protection | |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 4.8 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of tight fit on support | Test passed |
Setpoint | 5 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 4.8 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 300 A |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 500 A |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 150 A |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 1250 A |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 2, bogie-mounted |
Test frequency | f1= 5 Hz to f2= 250 Hz |
ASD level | 6.12 (m/s2)2/Hz |
Acceleration | 3.12 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Connection data
Connection method | Ring cable lug |
---|---|
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Min. AWG conductor cross section, flexible | 24 |
Max. AWG conductor cross section, flexible | 8 |
2 conductors with same cross section, solid min. | 0.5 mm² |
2 conductors with same cross section, solid max. | 6 mm² |
2 conductors with same cross section, stranded min. | 0.5 mm² |
2 conductors with same cross section, stranded max. | 6 mm² |
Cable lug connection according to standard | DIN 46234 |
Min. cross section for cable lug connection | 0.5 mm² |
Max. cross section for cable lug connection | 10 mm² |
Hole diameter, min. | 4.3 mm |
Cable lug width, max. | 8 mm |
Bolt diameter | 4.1 mm |
Cable lug connection according to standard | DIN 46237 |
Min. cross section for cable lug connection | 0.5 mm² |
Max. cross section for cable lug connection | 10 mm² |
Hole diameter, min. | 4.3 mm |
Cable lug width, max. | 8 mm |
Bolt diameter | 4.1 mm |
Stripping length | 12 mm |
Internal cylindrical gage | A5 |
Screw thread | No 8 UNC |
Tightening torque, min | 1.5 Nm |
Tightening torque max | 1.8 Nm |
Mounting
Mounting type | Wall mounting |
---|---|
Plate thickness | 1 mm … 4 mm |
Min. tightening torque of the mounting screw: | 0.8 Nm |
Max. tightening torque of the mounting screw: | 1 Nm |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-1 |
---|---|
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |