Key Commercial Data
Orderkey | 2907027 |
---|---|
Packing unit | 10 pc |
Catalog page | Page 322 (C-5-2017) |
GTIN | 4055626159959 |
Weight per Piece (excluding packing) | 92.000 g |
Custom tariff number | 85364900 |
Country of origin | PL (Poland) |
Ambient conditions
Ambient temperature (operation) | -40 °C … 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Coil side
Nominal input voltage UN | 220 V DC |
---|---|
Input voltage range in reference to UN | see diagram |
Typical input current at UN | 8 mA |
Typical response time | 18 ms |
Typical release time | 7 ms |
Protective circuit | Damping diode |
Status display | Yellow LED |
Power dissipation for nominal condition | 1.76 W |
Contact side
Contact type | 3 PDTs |
---|---|
Type of switch contact | Single contact |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 10 V (At 24 mA) |
Min. switching current | 10 mA (at 24 V) |
Maximum inrush current | 30 A (20 ms, N/O contact) |
Limiting continuous current | 10 A |
Interrupting rating (ohmic load) max. | 240 W (at 24 V DC) |
124 W (at 48 V DC) | |
108 W (at 60 V DC) | |
52 W (at 110 V DC) | |
48 W (at 220 V DC) | |
2500 VA (for 250 V AC) | |
Switching capacity min. | 0.24 W |
Switching capacity | 2 A (at 24 V, DC13) |
1.5 A (at 230 V, AC15) |
General
Test voltage relay winding/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
---|---|
Test voltage PDT/PDT | 2 kVrms(50 Hz, 1 min.) |
Operating mode | 100% operating factor |
Degree of protection | RT I |
Mechanical service life | 1x 107cycles, approximately |
Mounting position | any |
Net weight (SAP) | 92 g |