Key Commercial Data
Orderkey | 1081818 |
---|---|
Packing unit | 1 pc |
Minimum order quantity | 50 pc |
GTIN | 4055626810065 |
Weight per Piece (excluding packing) | 0.000 g |
Custom tariff number | 85176200 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -20 °C … 70 °C |
-4 °F … 158 °F | |
Ambient temperature (storage/transport) | -20 °C … 70 °C |
-4 °F … 158 °F | |
Permissible humidity (operation) | 20 % … 85 % |
Permissible humidity (storage/transport) | 20 % … 85 % |
Altitude | 2000 m |
Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz … 150 Hz |
Shock | 16g, 11 ms |
General
Operating mode | Serial data (Activation and configuration via PSI-CONF software) |
---|---|
Overvoltage category | II |
Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
Degree of pollution | 2 |
Housing material | PA 6.6-FR |
Flammability rating according to UL 94 | V0 |
MTTF | 778 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
358 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
142 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
Wireless licences | Belgium |
Bulgaria | |
Denmark | |
Germany | |
Estonia | |
France | |
Finland | |
Greece | |
Great Britain | |
Italy | |
Ireland | |
Iceland | |
Canada (IC, RSS 210, ID: 4720B-RAD2400A) | |
Croatia | |
Liechtenstein | |
Luxembourg | |
Latvia | |
Lithuania | |
Malta | |
Netherlands | |
Norway | |
Austria | |
Poland | |
Portugal | |
Romania | |
Sweden | |
Switzerland | |
Slovakia | |
Slovenia | |
Spain | |
Czech Republic | |
Turkey | |
Hungary | |
USA (FCC, Part 15.247, ID: YG3RAD2400A) | |
Cyprus (rep.) | |
India (WPC, ID: NER-ETA/314) | |
Brazil (ANATEL, ID: 06279-19-06497) |
Supply
Supply voltage range | 19.2 V DC … 30.5 V DC |
---|---|
Max. current consumption | ≤ 48 mA (at 24 V DC, at 25 °C) |
Transient surge protection | Yes |
Wireless interface
Antenna connection | RSMA (female) |
---|---|
Direction | Bi-directional |
Frequency | 2400 MHz |
Frequency range | 2.4002 GHz … 2.4785 GHz |
Number of channel groups | 8 |
Number of channels per group | 55 |
Channel distance | 1.3 MHz |
Data rate | 16 kbps (adjustable) |
125 kbps (Default setting, adjustable) | |
250 kbps (adjustable) | |
Receiver sensitivity | -106 dBm (16 kbps) |
-96 dBm (125 kbps) | |
-93 dBm (250 kbps) | |
Transmit capacity, minimum | 0 dBm |
Transmit capacity, maximum | ≤ 18 dBm (can be set via software) |
Range | ± 500 m (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used) |
Serial interface
Interface 1 | RS-485 |
---|---|
Connection method | COMBICON plug-in screw terminal block |
Connection technology | 2-wire |
Transmission length | ≤ 1200 m |
Termination resistor | 390 Ω (switchable via DIP switches) |
150 Ω (switchable via DIP switches) | |
390 Ω (switchable via DIP switches) | |
Transmission speed | 0.3 … 115.2 kbps |
Interface 2 | Configuration interface |
Connection method | S-PORT (socket) |
System limits
Designation | Wireless module |
---|---|
Number of supported devices | ≤ 250 (Addressing via PSI-CONF software) |
Connection data
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Tightening torque | 0.6 Nm |
Screw thread | M3 |
Status indicator
Status display | Green LED (supply voltage, PWR) |
---|---|
LED yellow (reception quality, LINK) | |
Green LED (receive data, RX) | |
Green LED (transmit data, TX) |
Conformance/approvals
Designation | CE |
---|---|
Identification | CE-compliant |
Additional text | RED 2014/53/EU |
Designation | FCC |
Additional text | FCC directive, part 15.247 |
Designation | ISC |
Additional text | ISC directive RSS 210 |
Designation | UL, USA/Canada |
Identification | 508 Listed |
Designation | ANATEL |
Certificate | 06279-19-06497 |
Standards and Regulations
Electromagnetic compatibility | Conformance with RED Directive 2014/53/EU |
---|---|
Standards/specifications | RED directive 2014/53/EU EN 300328 EN 61000-6-4 EN 61000-6-2 EN 50371 EN 60950-1 |
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV (Test Level 3) |
Indirect discharge | ± 6 kV |
Standards/regulations | EN 61000-4-3 |
Frequency range | 26 MHz … 3 GHz (Test Level 3) |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Signal | ± 1 kV (asymmetrical) |
Standards/regulations | EN 61000-4-6 |
Frequency range | 0.15 MHz … 80 MHz |
Flammability rating according to UL 94 | V0 |
Interface description | Trusted Wireless |
Channel distance | 1.3 MHz |
Shock | 16g, 11 ms |
Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz … 150 Hz |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |
Classifications
[email protected]
[email protected] 10.0.1 | 19179290 |
---|---|
[email protected] 6.0 | 19179200 |
[email protected] 7.0 | 19179290 |
[email protected] 8.0 | 19179290 |
[email protected] 9.0 | 19179290 |