Key Commercial Data
Orderkey | 2904601 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 206 (C-4-2017) |
GTIN | 4046356985338 |
Weight per Piece (excluding packing) | 1,104.400 g |
Custom tariff number | 85044030 |
Country of origin | TH (Thailand) |
Dimensions
Width | 50 mm |
---|---|
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 53 mm |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
110 V DC … 250 V DC | |
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
Dielectric strength maximum | 300 V AC 60 s |
AC frequency range | 50 Hz … 60 Hz -10 % … +10 % |
Discharge current to PE | < 3.5 mA |
Current consumption | 3.4 A (100 V AC) |
2.8 A (120 V AC) | |
1.5 A (230 V AC) | |
1.5 A (240 V AC) | |
Nominal power consumption | 274 VA |
Inrush surge current | typ. 18 A (at 25 °C) |
Mains buffering | typ. 42 ms (120 V AC) |
typ. 44 ms (230 V AC) | |
Input fuse | 8 A (slow-blow, internal) |
Choice of suitable circuit breakers | 10 A … 16 A (Characteristic B, C, D, K or comparable) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
Nominal output voltage | 24 V DC |
---|---|
Setting range of the output voltage (USet) | 24 V DC … 29.5 V DC (constant capacity) |
Nominal output current (IN) | 10 A |
Static Boost (IStat.Boost) | 12.5 A |
Dynamic Boost (IDyn.Boost) | 20 A (5 s) |
Selective Fuse Breaking (ISFB) | 60 A (15 ms) |
Derating | > 60 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | ≤ 35 V DC |
Protection against surge voltage on the output | ≤ 32 V DC |
Control deviation | < 0.5 % (Static load change 10 % … 90 %) |
< 4 % (Dynamic load change 10 % … 90 %, (10 Hz)) | |
< 0.25 % (change in input voltage ±10 %) | |
Residual ripple | < 80 mVPP(with nominal values) |
Output power | 240 W |
Typical response time | 300 ms (from SLEEP MODE) |
Maximum power dissipation in no-load condition | < 3 W (120 V AC) |
< 3 W (230 V AC) | |
Power loss nominal load max. | < 20 W (120 V AC) |
< 17 W (230 V AC) |
General
Net weight | 0.9 kg |
---|---|
Efficiency | typ. 92.5 % (120 V AC) |
typ. 93.4 % (230 V AC) | |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 3.5 kV AC (type test) |
2.4 kV AC (routine test) | |
Insulation voltage output / PE | 0.5 kV DC (type test) |
0.5 kV DC (routine test) | |
Protection class | I |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1250000 h (25 °C) |
> 783000 h (40 °C) | |
> 377000 h (60 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |