Key Commercial Data
Orderkey | 2904605 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 252 (C-4-2019) |
GTIN | 4055626255736 |
Weight per Piece (excluding packing) | 240.000 g |
Custom tariff number | 85044030 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
---|---|
110 V DC … 250 V DC -20 % … +40 % | |
Dielectric strength maximum | 300 V AC 60 s |
Frequency range (fN) | 50 Hz … 60 Hz -10 % … +10 % |
Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
Current consumption | 0.44 A (100 V AC) |
0.35 A (120 V AC) | |
0.19 A (230 V AC) | |
0.2 A (240 V AC) | |
Nominal power consumption | 32.8 VA |
Inrush current | typ. 11.3 A (at 25 °C) |
Mains buffering time | typ. 54 ms (120 V AC) |
typ. 54 ms (230 V AC) | |
Input fuse | 3.15 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A … 16 A (Characteristic B, C or comparable) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 12 V DC |
---|---|
Setting range of the output voltage (USet) | 12 V DC … 15 V DC (constant capacity) |
Nominal output current (IN) | 2.5 A |
Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 4.5 A (≤ 60 °C (5 s)) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | ≤ 25 V DC |
Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
Control deviation | < 0.2 % (Static load change 10 % … 90 %) |
< 2 % (Dynamic load change 10 % … 90 %, (10 Hz)) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 30 mVPP(with nominal values) |
Output power | 30 W |
Typical response time | 500 ms |
Maximum power dissipation in no-load condition | < 0.4 W (230 V AC) |
< 0.5 W (120 V AC) | |
Power loss nominal load max. | < 3.5 W (120 V AC) |
< 3 W (230 V AC) |
General
Net weight | 0.181 kg |
---|---|
Efficiency | typ. 89.5 % (120 V AC) |
typ. 90.9 % (230 V AC) | |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) | |
Protection class | II |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1848000 h (25 °C) |
> 1060000 h (40 °C) | |
> 459000 h (60 °C) |
Connection data, input
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Connection data, output
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Connection data for signaling
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Standards
Standard – Safety of transformers | EN 61558-2-16 |
---|---|
Standard – safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard – Safe isolation | IEC 61558-2-16 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Conformance/approvals
UL approvals | UL Listed UL 61010-1 |
---|---|
UL Listed UL 61010-2-201 | |
UL 1310 Class 2 Power Units | |
ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
EMC data
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Flicker | EN 61000-3-3 |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz … 1 GHz |
Test field strength | 20 V/m (Test Level X) |
Frequency range | 1 GHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 4 kV (Test Level X – asymmetrical) |
Signal | 4 kV (Test Level X – asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 2 kV (Test Level 4 – symmetrical) |
4 kV (Test Level 4 – asymmetrical) | |
Output | 1 kV (Test Level 3 – symmetrical) |
2 kV (Test Level 3 – asymmetrical) | |
Signal | 0.5 kV (Test Level 2 – symmetrical) |
Comments | Criterion A |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz … 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Frequency | 16.67 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips | EN 61000-4-11 |
Voltage | 100 V AC |
Frequency | 60 Hz |
Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 30 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Voltage dip | 0 % |
Number of periods | 0.5 / 1 / 5 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Pulse-shape magnetic field | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
Input | 2 kV (symmetrical) |
4 kV (asymmetrical) | |
Comments | Criterion A |
Asymmetrical conducted disturbance variables | EN 61000-4-16 |
Test level 1 | 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) |
Voltage | 30 V (10 s) |
Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 2) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave | EN 61000-4-18 |
Voltage | 1 kV (symmetrical) |
2.5 kV (asymmetrical) | |
1 kV (symmetrical) | |
Comments | Criterion A |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Classifications
[email protected]
[email protected] 5.1 | 27242213 |
---|---|
[email protected] 6.0 | 27049000 |
[email protected] 7.0 | 27049002 |
[email protected] 8.0 | 27049002 |
[email protected] 9.0 | 27040701 |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |