Key Commercial Data
Orderkey | 2905009 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 253 (C-4-2017) |
GTIN | 4046356908436 |
Weight per Piece (excluding packing) | 1,189.500 g |
Custom tariff number | 85044030 |
Country of origin | CN (China) |
Dimensions
Width | 48 mm |
---|---|
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 51 mm |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Input data
Nominal input voltage range | 60 V DC … 72 V DC |
---|---|
Input voltage range | 42 V DC … 96 V DC |
Current consumption | 5.6 A (60 V DC) |
4.7 A (72 V DC) | |
Inrush surge current | < 9 A (typical) |
Mains buffering | typ. 10 ms (60 V DC) |
Input fuse | 10 A 150 V DC (internal (device protection)) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (-40 °C … 60 °C) |
POWER BOOST (IBoost) | 12.5 A (-40°C … 40°C permanent, UOUT= 24 V DC ) |
Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
Derating | 60 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | 35 V DC |
Protection against surge voltage on the output | < 35 V DC |
Max. capacitive load | unlimited |
Active current limitation | 18 A |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 20 mVPP |
Peak switching voltages nominal load | < 10 mVPP(20 MHz) |
Maximum power dissipation in no-load condition | 4 W (UIN60 V DC) |
Power loss nominal load max. | 24 W (UIN60 V DC) |
General
Net weight | 1 kg |
---|---|
Efficiency | > 91 % (UIN60 V DC / UOUT24 V DC) |
> 91 % (UIN72 V DC / UOUT24 V DC) | |
Insulation voltage input/output | 1.5 kV (type test) |
1 kV (routine test) | |
Protection class | I |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1349000 h (25 °C) |
> 765000 h (40 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |