Key Commercial Data
| Orderkey | 2938633 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 411 (IF-2002) |
| GTIN | 4017918910983 |
| Weight per Piece (excluding packing) | 3,300.000 g |
| Custom tariff number | 85044030 |
| Country of origin | DE (Germany) |
Dimensions
| Width | 240 mm |
|---|---|
| Height | 130 mm |
| Depth | 130 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 243 mm |
| Depth with alternative assembly | 243 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Input data
| Nominal input voltage range | 3x 400 V AC … 500 V AC |
|---|---|
| Input voltage range | 3x 320 V AC … 575 V AC (for all three phases) |
| 450 V DC … 800 V DC | |
| AC frequency range | 45 Hz … 65 Hz |
| Frequency range DC | 0 Hz |
| Current consumption | approx. 3x 2.1 A (400 V AC) |
| 3x 1.7 A (480 V AC) | |
| Nominal power consumption | 720 W |
| Inrush surge current | < 15 A (typical) |
| Mains buffering | > 20 ms (at 3 x 400 V AC) |
| > 20 ms (at 3 x 480 V AC) | |
| Input fuse | Externally via 3 circuit breakers 6 A, 10 A or 16 A, characteristic B |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 22.5 V … 28.5 V |
| Nominal output current (IN) | 30 A (up to 60°C) |
| POWER BOOST (IBoost) | 35 A |
| Connection in parallel | Yes, for assembling redundant systems and increasing efficiency |
| Connection in series | yes |
| Residual ripple | < 100 mVPP |
| Output power | 720 W |
| Typical response time | < 1 s |
| Peak switching voltages nominal load | < 100 mVPP(20 MHz) |
| Maximum power dissipation in no-load condition | < 14 W |
| Power loss nominal load max. | < 62 W |
General
| Net weight | 3.3 kg |
|---|---|
| Operating voltage display | Green LED |
| Efficiency | > 92 % |
| Insulation voltage input/output | 2 kV (routine test) |
| 4 kV (type test) | |
| Protection class | I (with PE connection) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 500000 h |
| Mounting position | On horizontal DIN rail NS 35 in acc. with EN 60715 |
| Assembly instructions | alignable: vertical with spacing = 5 cm |