Key Commercial Data
| Orderkey | 2866789 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 210 (C-4-2017) |
| GTIN | 4046356421720 |
| Weight per Piece (excluding packing) | 3,798.800 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 180 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 183 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | 4000 m |
Input data
| Nominal input voltage range | 100 V AC … 240 V AC |
|---|---|
| 120 V DC … 300 V DC (UL 508: ≤ 250 V DC) | |
| Input voltage range | 85 V AC … 264 V AC |
| 90 V DC … 300 V DC (UL 508: ≤ 250 V DC) | |
| Dielectric strength maximum | 300 V AC |
| AC frequency range | 45 Hz … 65 Hz |
| Frequency range DC | 0 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 8.8 A (120 V AC) |
| 4.6 A (230 V AC) | |
| 9.5 A (110 V DC) | |
| 4.7 A (220 V DC) | |
| Nominal power consumption | 1157 VA |
| Inrush surge current | < 15 A (typical) |
| Mains buffering | > 35 ms (120 V AC) |
| > 35 ms (230 V AC) | |
| Input fuse | 20 A (slow-blow, internal) |
| Choice of suitable circuit breakers | 16 A … 20 A (AC: Characteristics B, C, D, K) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 40 A (-25 °C … 60 °C, UOUT= 24 V DC) |
| POWER BOOST (IBoost) | 45 A (-25°C … 40°C permanent, UOUT= 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 215 A (12 ms) |
| Derating | 60 °C … 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | max. 35 V DC |
| Output overvoltage protection | < 35 V DC |
| Residual ripple | < 30 mVPP(with nominal values) |
| Output power | 960 W |
| Typical response time | < 0.7 s |
| Maximum power dissipation in no-load condition | 14 W |
| Power loss nominal load max. | 80 W |
General
| Net weight | 3.3 kg |
|---|---|
| Efficiency | > 92 % (for 230 V AC and nominal values) |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage input / PE | 3.5 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage output / PE | 500 V DC (routine test) |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 900000 h (25 °C) |
| > 530000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |