Key Commercial Data
Orderkey | 2866747 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 210 (C-4-2017) |
GTIN | 4046356113779 |
Weight per Piece (excluding packing) | 500.000 g |
Custom tariff number | 85044030 |
Country of origin | TH (Thailand) |
Dimensions
Width | 32 mm |
---|---|
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 35 mm |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | 5000 m |
Input data
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
Input voltage range | 85 V AC … 264 V AC |
90 V DC … 350 V DC | |
Dielectric strength maximum | 300 V AC |
AC frequency range | 45 Hz … 65 Hz |
Frequency range DC | 0 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 1.4 A (120 V AC) |
0.8 A (230 V AC) | |
0.9 A (110 V DC) | |
0.4 A (220 V DC) | |
Nominal power consumption | 180 VA |
Inrush surge current | < 20 A (typical) |
Mains buffering | typ. 20 ms (120 V AC) |
typ. 80 ms (230 V AC) | |
Input fuse | 5 A (slow-blow, internal) |
Choice of suitable circuit breakers | 6 A … 20 A (AC: Characteristics B, C, D, K) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 3.5 A (-25 °C … 60 °C, UOUT= 24 V DC) |
POWER BOOST (IBoost) | 4 A (-25°C … 40°C permanent, UOUT= 24 V DC ) |
Selective Fuse Breaking (ISFB) | 15 A (12 ms) |
Derating | 60 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | max. 35 V DC |
Output overvoltage protection | < 35 V DC |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 50 mVPP(with nominal values) |
Output power | 84 W |
Typical response time | < 0.05 s |
Maximum power dissipation in no-load condition | 3.5 W |
Power loss nominal load max. | 11 W |
General
Net weight | 0.5 kg |
---|---|
Operating voltage display | Green LED |
Efficiency | > 88 % (for 230 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 3.5 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage output / PE | 500 V DC (routine test) |
Protection class | I |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1433000 h (25 °C) |
> 820000 h (40 °C) | |
> 360000 h (60 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |