Key Commercial Data
Orderkey | 2866585 |
---|---|
Packing unit | 1 pc |
GTIN | 4046356494458 |
Weight per Piece (excluding packing) | 679.000 g |
Custom tariff number | 85049091 |
Country of origin | CN (China) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C derating, -25 … 60°C) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Degree of pollution | 2 |
Input data
Nominal input voltage | 48 V DC (UN) |
---|---|
< 60 V DC (Umax) | |
Input voltage range | 10 V DC … 60 V DC |
Nominal input current | 2x 20 A |
1x 40 A | |
Maximum input current | 2x 19 A (6 mm² at 40°C) |
1x 39 A (6 mm² at 40°C) | |
2x 16 A (6 mm² at 60°C) | |
1x 32 A (6 mm² at 60°C) | |
2x 27 A (10 mm² at 40°C) | |
1x 54 A (10 mm² at 40°C) | |
2x 21 A (10 mm² at 60°C) | |
1x 43 A (10 mm² at 60°C) | |
2x 30 A (16 mm² at 40 °C) | |
1x 60 A (16 mm² at 40 °C) | |
2x 24 A (16 mm² at 60°C) | |
1x 48 A (16 mm² at 60°C) | |
Nominal input current | 2x 20 A |
1x 40 A | |
Maximum input current | 2x 17 A (6 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
1x 35 A (6 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
2x 14 A (6 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
1x 28 A (6 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
2x 24 A (10 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
1x 49 A (10 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
2x 19 A (10 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
1x 39 A (10 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
2x 27 A (16 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
1x 54 A (16 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
2x 22 A (16 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) | |
1x 44 A (16 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
Output data
Nominal output voltage | 47.3 V DC (Input/output voltage drop of 48 V … 0.7 V ) |
---|---|
Nominal output current (IN) | 40 A |
Connection in series | No |
Power loss nominal load max. | 28 W |
General
Net weight | 0.7 kg |
---|---|
Efficiency | > 97 % |
Insulation voltage input / PE | 1 kV |
Insulation voltage output / PE | 1 kV |
Protection class | II |
Degree of protection | IP20 |
Mounting position | horizontal and vertical DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontal 20 mm, vertical 50 mm |