Key Commercial Data
Orderkey | 2866226 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 587 (IF-2009) |
GTIN | 4017918959722 |
Weight per Piece (excluding packing) | 1,800.000 g |
Custom tariff number | 85371091 |
Country of origin | CN (China) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | 0 °C … 50 °C |
Ambient temperature (storage/transport) | 0 °C … 40 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Input data
Nominal input voltage | 24 V DC |
---|---|
Input voltage range | 22.5 V DC … 30 V DC |
Current consumption | approx. 0.1 A |
0.5 A (charging process) | |
10.5 A (max.) | |
Current consumption (maximum) | 10.5 A (max.) |
Current consumption (idle) | approx. 0.1 A |
Current consumption (charging process) | 0.5 A (charging process) |
Buffer period | 1.5 min. (10 A) |
20 min. (2 A) | |
Input fuse | 15 A (slow-blow, internal) |
Output data
Nominal output voltage | 24 V DC (Normal operation: Uin– 0.5 V DC, buffer mode: 27.9 to 19.2 V DC) |
---|---|
Nominal output current (IN) | 10 A |
Connection in parallel | No |
Connection in series | yes |
Output power | 240 W |
General
Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer. |
---|---|
Net weight | 1.8 kg |
Memory medium | Internal, battery 1.3 Ah |
Operating voltage display | Green LED |
Efficiency | > 91 % |
Insulation voltage input/output | 2 kV (routine test) |
4 kV (type test) | |
Protection class | II (in closed control cabinet) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |