Key Commercial Data
Orderkey | 3050248 |
---|---|
Packing unit | 50 pc |
Minimum order quantity | 50 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 207 (C-1-2017) |
GTIN | 4017918975890 |
Weight per Piece (excluding packing) | 18.600 g |
Custom tariff number | 85369010 |
Country of origin | PL (Poland) |
General
Number of levels | 2 |
---|---|
Number of connections | 4 |
Nominal cross section | 1.5 mm² |
Color | green-yellow |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Connection method | Quick connection |
Connection in acc. with standard | IEC 60947-7-2 |
Connection method | Spring-cage connection |
Connection in acc. with standard | IEC 60947-7-2 |
Open side panel | Yes |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Dimensions
Width | 5.2 mm |
---|---|
Length | 88.2 mm |
Height NS 35/7,5 | 49.9 mm |
Height NS 35/15 | 57.4 mm |
End cover width | 2.2 mm |
Connection data
Connection method | Quick connection |
---|---|
Connection in acc. with standard | IEC 60947-7-2 |
Note | Please observe the current carrying capacity of the DIN rails. |
Max. wire diameter incl. insulation | 3 mm |
Conductor cross section solid min. | 0.25 mm² |
Conductor cross section solid max. | 1.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 |
Conductor cross section flexible min. | 0.25 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Min. AWG conductor cross section, flexible | 24 |
Max. AWG conductor cross section, flexible | 16 |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 1.5 mm² |
Conductor cross section flexible min. after 10 connections with the max. solid conductor | 0.25 mm² |
Conductor cross section flexible max. after 10 connections with the max. solid conductor | 1.5 mm² |
Conductor cross section solid min. after 10 connections with the max. solid conductor | 0.25 mm² |
Conductor cross section solid max. after 10 connections with the max. solid conductor | 1.5 mm² |
AWG min. after 10 connections with the max. rigid conductor | 24 |
AWG max. after 10 connections with the max. rigid conductor | 16 |
Cross section sensor cables, min. | 0.25 mm² |
Cross section sensor cables, max. | 0.34 mm² |
Material wire insulation | PVC / PE |
Standards and Regulations
Connection in acc. with standard | CUL |
---|---|
IEC 60947-7-2 | |
IEC 60947-7-2 | |
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |