Ambient conditions
Ambient temperature (operation) | -40 °C … 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Altitude | ≤ 4000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
General
Housing material | PA 6.6 |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | jet black RAL 9005 |
Mounting type | DIN rail: 35 mm |
Type | DIN rail module, two-section, divisible |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Additional descriptions
Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
---|
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 48 V DC |
Maximum continuous voltage UC | 53 V DC |
37 V AC | |
Rated current | 300 mA |
Operating effective current IC at UC | ≤ 5 µA (in the signal circuit) |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In (8/20) µs (line-line) | 10 kA |
Nominal discharge current In (8/20) µs (line-earth) | 10 kA |
Nominal discharge current In (8/20) µs (core-signal ground) | 10 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 2.5 kA |
Total discharge current Itotal (8/20) µs | 20 kA |
Voltage protection level Up (line-line) | ≤ 100 V (C1 – 1 kV/500 A) |
≤ 150 V (C2 – 10 kV / 5 kA) | |
≤ 90 V (C3 – 25 A) | |
≤ 95 V (C3 – 100 A) | |
Voltage protection level Up (line-earth) | ≤ 900 V (C1 – 1 kV/500 A) |
≤ 1300 V (C2 – 10 kV / 5 kA) | |
≤ 1000 V (C3 – 25 A) | |
≤ 1300 V (C3 – 100 A) | |
Voltage protection level Up (line-signalground) | ≤ 600 V (C1 – 1 kV/500 A) |
≤ 750 V (C2 – 10 kV / 5 kA) | |
≤ 700 V (C3 – 25 A) | |
≤ 800 V (C3 – 100 A) | |
Voltage protection level Up static (line-earth) | ≤ 130 V (C2 – 10 kV / 5 kA) |
≤ 60 V (C3 – 25 A) | |
Voltage protection level Up static (line-signalground) | ≤ 60 V (C2 – 10 kV / 5 kA) |
≤ 40 V (C3 – 25 A) | |
≤ 100 V (C3 – 100 A) | |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-signalground) | ≤ 100 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 450 kHz/150 Ω) |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1.9 MHz |
Capacity (line-line) | typ. 1.5 nF |
Resistance in series | 1.2 Ω ±5 % |
Surge protection fault message | Optical, multi-stage |
Max. required back-up fuse | 315 mA (FF) |
Impulse durability (line-line) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 100 A | |
Impulse durability (line-earth) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 100 A | |
D1 – 2.5 kA | |
Impulse durability (line-signalground) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 100 A | |
Pulse reset time (line-line) | ≤ 300 ms |
Pulse reset time (line-earth) | ≤ 30 ms |
Pulse reset time (line-signalground) | ≤ 4000 ms |