Key Commercial Data
Orderkey | 3044929 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Note | Made to Order (non-returnable) |
GTIN | 4055626303178 |
Weight per Piece (excluding packing) | 150.040 g |
Custom tariff number | 85369010 |
Country of origin | PL (Poland) |
General
Note | Assembly instruction: Minimum distance to other conductive surfaces: min 5 mm |
---|---|
Number of positions | 24 |
Number of levels | 1 |
Number of connections | 44 |
Potentials | 24 |
Nominal cross section | 2.5 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Degree of pollution | 3 |
Overvoltage category | III |
Maximum power dissipation for nominal condition | 1.02 W (the value is based on one connection block and is multiplied according to the pin assignment) |
Ambient temperature (operation) | -50 °C … 85 °C |
Maximum load current | 30 A (with 4 mm² conductor cross section) |
Nominal current IN | 24 A |
Nominal voltage UN | 500 V |
Open side panel | No |
Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 7.3 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test conductor cross section/weight | 0.14 mm² / 0.2 kg |
2.5 mm² / 0.7 kg | |
4 mm² / 0.9 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.14 mm² |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 2.5 mm² |
Tractive force setpoint | 50 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 3.2 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.15 kA |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 0.15 kA |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 0.3 kA |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.5 kA |
Result of thermal test | Test passed |
Ageing test for screwless modular terminal block temperature cycles | 192 |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Result of aging test | Test passed |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 1, class B, body mounted |
Test frequency | f1= 5 Hz to f2= 150 Hz |
ASD level | 0.964 (m/s2)2/Hz |
Acceleration | 0.58 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 5 g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Connection data
Note | Derating curve on request. |
---|---|
Connection method | Push-in connection |
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section solid min. | 0.14 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 4 mm² |
Min. AWG conductor cross section, flexible | 26 |
Max. AWG conductor cross section, flexible | 12 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 2.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 0.5 mm² |
Stripping length | 10 mm … 12 mm |
Internal cylindrical gage | A3 |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-1 |
---|---|
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |