Key Commercial Data
Orderkey | 2702925 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 263 (C-6-2017) |
GTIN | 4055626428895 |
Weight per Piece (excluding packing) | 195.000 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -20 °C … 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
Rated control circuit supply voltage US | 42 V AC/DC … 230 V AC/DC -15 % … +10 % (Rated control circuit supply voltage US) |
---|---|
Rated control supply current IS | typ. 35 mA (42 V DC) |
typ. 15 mA (230 V AC) | |
Power consumption at US | max. 1.5 W (with DC) |
max. 1.7 W (with AC) | |
Inrush current | < 38 A (Δt = 50 µs at Us) |
Typ. starting time with Us | < 100 ms (when controlled via A1) |
Typical release time | < 20 ms (Control via A1 at 42 V DC) |
< 200 ms (Control via A1 at 230 V AC) | |
Recovery time | < 1 s |
Operating voltage display | 1 x green LED |
Protective circuit | Surge protection Suppressor diode and varistors |
Maximum switching frequency | 0.5 Hz |
Output data
Contact type | 4 enabling current paths |
---|---|
1 confirmation current path | |
1 signaling current path | |
Contact material | AgSnO2 |
Maximum switching voltage | 250 V AC/DC (Observe the load curve) |
Minimum switching voltage | 5 V AC/DC |
Limiting continuous current | 6 A (N/O contact, pay attention to the derating) |
1 A (N/C contact 51/52) | |
6 A (N/C contact 61/62) | |
Maximum inrush current | 8 A |
Inrush current, minimum | 10 mA |
Sq. Total current | 72 A2(observe derating) |
Interrupting rating (ohmic load) max. | 1500 VA (N/O contact, 250 V AC, τ = 0 ms) |
For additional values, see load curve | |
Maximum interrupting rating (inductive load) | 48 W (N/O contact, 24 V DC, τ = 40 ms) |
40 W (N/O contact, 48 V DC, τ = 40 ms) | |
36 W (N/O contact, 60 V DC, τ = 40 ms) | |
35 W (N/O contact, 110 V DC, τ = 40 ms) | |
33 W (N/O contact, 220 V DC, τ = 40 ms) | |
1500 VA (N/O contact, 250 V AC, τ = 40 ms) | |
Switching capacity | min. 50 mW |
Mechanical service life | 10x 106cycles |
Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
5 A (250 V (AC15)) | |
Output fuse | 6 A gL/gG (N/O contact and N/C contact 61/62) |
4 A gL/gG (N/O contact and N/C contact 61/62 for low-demand applications) | |
1 A gL/gG (N/C contact 51/52) |