Key Commercial Data
| Orderkey | 2986106 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 294 (C-6-2017) |
| GTIN | 4046356536547 |
| Weight per Piece (excluding packing) | 220.000 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C … 70 °C |
| Max. permissible relative humidity (operation) | 75 % (On average, 85 % occasionally) |
| Max. permissible humidity (storage/transport) | 75 % (On average, 85 % occasionally) |
| Air pressure (operation) | 70 kPa … 108 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 66 kPa … 108 kPa (up to 3500 m above sea level) |
| Maximum altitude | max. 2000 m (See Appendix “Using PSR-TRISAFE modules at altitudes greater than 2000 m above sea level”) |
Power supply
| Rated control circuit supply voltage US | 24 V DC (Electrical supply via PSR-TBUS) |
|---|---|
| 18 V DC … 30 V DC (Incl. all tolerances, incl. residual ripple) | |
| Rated control supply current IS | Electrical supply via PSR-TBUS |
| 74 mA (At 24 V DC, relay outputs set) | |
| 54 mA (At 24 V DC, relay outputs not set) | |
| Status display | 1 x green LED, 1 x red LED |
| Protective circuit | Yes, within the scope of the operating voltage limits |
Relay outputs: enabling current path
| Output description | Relay contacts, safety-related N/O contacts |
|---|---|
| Number of outputs | 4 (Single-channel) |
| 2 (Two-channel, connected in pairs) | |
| Contact type | 4 relay output contacts |
| Contact material | AgSnO2(From HW03) AgCuNi + 0.2 – 0.4 μm Au (up to HW02) |
| Switching voltage | min. 12 V AC/DC (from HW 03) |
| min. 5 V AC/DC (Up to HW02) | |
| max. 250 V AC/DC | |
| Limiting continuous current | 4 A (see to derating) |
| Switching current | min. 3 mA (from HW 03) |
| min. 5 mA (Up to HW02) | |
| Switching capacity | min. 60 mW |
| Mechanical service life | 10x 106cycles |
| Output fuse | 6 A (gL / gG) |
| 4 A (gL/gG for low-demand applications) | |
| Status display | 4 x green LEDs |