Key Commercial Data
Orderkey | 2981981 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 286 (C-6-2017) |
GTIN | 4046356448345 |
Weight per Piece (excluding packing) | 99.990 g |
Custom tariff number | 85364900 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -20 °C … 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 70 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
---|---|
Rated control supply current IS | typ. 55 mA |
Power consumption at US | typ. 1.32 W |
Inrush current | max. 100 mA |
Typ. starting time with Us | 50 ms |
Typical release time | 50 ms |
Recovery time | 1 s |
Operating voltage display | 1 x yellow LED |
Protective circuit | Surge protection Suppressor diode, 33 V (A1 – A2) |
Maximum switching frequency | 0.5 Hz |
Filter time | max. 5 ms (at A1 in the event of voltage dips at Us) |
max. 2 ms (Test pulse width; high test pulse at A1/A2) | |
≥ 100 ms (Test pulse width; high test pulse at A1/A2) | |
Test pulse rate = 80 x Test pulse width | |
max. 5 ms (Test pulse width; low test pulse at A1/A2) | |
≥ 50 ms (Test pulse rate; low test pulse at A1/A2) | |
Test pulse rate = 15 x Test pulse width |
Output data
Contact type | 1 enabling current path |
---|---|
1 confirmation current path | |
Contact material | AgCuNi, + 0.2 µm Au |
Maximum switching voltage | 250 V AC/DC (N/O contact / N/C contact, observe the load curve) |
Minimum switching voltage | 15 V AC/DC (N/O contact / N/C contact) |
Limiting continuous current | 5 A (N/O contact, pay attention to the derating) |
100 mA (N/C contact) | |
Maximum inrush current | 5 A (N/O contact) |
100 mA (N/C contact) | |
Inrush current, minimum | 5 mA (N/O contact / N/C contact) |
Sq. Total current | 25 A2(observe derating) |
Interrupting rating (ohmic load) max. | 120 W (24 V DC, τ = 0 ms, N/C contact: 2.4 W) |
192 W (48 V DC, τ = 0 ms, N/C contact: 4.8 W) | |
162 W (60 V DC, τ = 0 ms, N/C contact: 6 W) | |
66 W (110 V DC, τ = 0 ms, N/C contact: 11 W) | |
60 W (220 V DC, τ = 0 ms, N/C contact: 22 W) | |
1250 VA (250 V AC, τ = 0 ms, N/C contact: 25 VA) | |
Maximum interrupting rating (inductive load) | 72 W (24 V DC, τ = 40 ms, N/C contact: 2.4 W) |
43 W (48 V DC, τ = 40 ms, N/C contact: 4.8 W) | |
41 W (60 V DC, τ = 40 ms, N/C contact: 6 W) | |
35 W (110 V DC, τ = 40 ms, N/C contact: 11 W) | |
48 W (220 V DC, τ = 40 ms, N/C contact: 22 W) | |
Switching capacity | min. 75 mW |
Mechanical service life | 10x 106cycles |
Output fuse | 5 A T fuse (N/O contact) |
150 mA Fast-blow (N/C contact) |