Ambient conditions
| Ambient temperature (operation) | -20 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | 120 V AC/DC -20 % … +10 % |
|---|---|
| Rated control supply current IS | typ. 11 mA |
| Power consumption at US | typ. 1.32 W |
| Inrush current | typ. 600 mA (Δt = 200 µs at Us) |
| Typ. starting time with Us | typ. 20 ms (when controlled via A1) |
| Typical release time | typ. 20 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Operating voltage display | 1 x green LED |
| Protective circuit | Surge protection Varistor |
| Maximum switching frequency | 0.5 Hz |
Output data
| Contact type | 5 enabling current paths |
|---|---|
| 2 confirmation current paths | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| 3 A (N/C contact) | |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) |
| 288 W (N/O contact, 48 V DC, τ = 0 ms) | |
| 240 W (N/O contact, 60 V DC, τ = 0 ms) | |
| 110 W (N/O contact, 110 V DC, τ = 0 ms) | |
| 88 W (N/O contact, 220 V DC, τ = 0 ms) | |
| 1380 VA (N/O contact, 230 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) |
| 42 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Mechanical service life | 10x 106 cycles |
| Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
| 4 A (250 V (AC15)) | |
| Switching capacity according to IEC 60947-5-1 | 3 A (24 V (DC13)) |
| 3 A (250 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 135.88 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Degree of protection | IP20 |
| IP54 | |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |