Key Commercial Data
Orderkey | 2981428 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 261 (C-6-2017) |
GTIN | 4017918975227 |
Weight per Piece (excluding packing) | 430.000 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C … 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 70 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
---|---|
Rated control supply current IS | typ. 155 mA |
Power consumption at US | typ. 3.72 W |
Inrush current | 200 mA (at US) |
< 40 mA (with Us/Ixto S10) | |
< 150 mA (with Us/Ixto S12) | |
> -60 mA (with Us/Ixto S22) | |
< 40 mA (with Us/Ixto S34) | |
< 40 mA (with Us/Ixto S35) | |
Current consumption | < 40 mA (with Us/Ixto S10) |
< 50 mA (with Us/Ixto S12) | |
> -40 mA (with Us/Ixto S22) | |
0 mA (with Us/Ixto S34) | |
< 5 mA (with Us/Ixto S35) | |
Voltage at input/start and feedback circuit | 24 V DC -15 % / +10 % |
Typical response time | < 600 ms (automatic start) |
< 70 ms (manual start) | |
Typ. starting time with Us | < 600 ms (when controlled via A1) |
Typical release time | < 20 ms (when controlled via S11/S12 and S21/S22) |
< 20 ms (when controlled via A1) | |
Concurrence input 1/2 | ∞ |
Recovery time | < 1 s |
Operating voltage display | 1 x green LED |
Status display | 4 x green LEDs |
Protective circuit | Surge protection Suppressor diode |
Maximum switching frequency | 0.5 Hz |
Max. permissible overall conductor resistance | approx. 22 Ω (Input and start circuits at US) |
Filter time | 1 ms (at A1 in the event of voltage dips at Us) |
max. 1.5 ms (at S10, S12; test pulse width) | |
7.5 ms (at S10, S12; test pulse rate) | |
Test pulse rate = 5 x Test pulse width |
Output data
Contact type | 5 enabling current paths |
---|---|
1 signaling current path | |
Contact material | AgSnO2 |
Maximum switching voltage | 250 V AC/DC (Observe the load curve) |
Minimum switching voltage | 5 V AC/DC |
Limiting continuous current | 6 A (N/O contact, pay attention to the derating) |
6 A (N/C contact) | |
Maximum inrush current | 20 A (Δt 100 ms, undelayed contacts) |
8 A (delayed contacts) | |
Inrush current, minimum | 10 mA |
Sq. Total current | 55 A2(observe derating) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
288 W (48 V DC, τ = 0 ms) | |
110 W (110 V DC, τ = 0 ms, delayed contacts: 77 W) | |
88 W (220 V DC, τ = 0 ms) | |
1500 VA (250 V AC, τ = 0 ms, delayed contacts: 2000 VA) | |
Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms, delayed contacts: 48 W) |
42 W (48 V DC, τ = 40 ms, delayed contacts: 40 W) | |
42 W (110 V DC, τ = 40 ms, delayed contacts: 35 W) | |
42 W (220 V DC, τ = 40 ms, delayed contacts: 33 W) | |
Switching capacity min. | 50 mW |
Mechanical service life | 10x 106cycles |
Switching capacity (360/h cycles) | 4 A (24 V DC) |
4 A (230 V AC) | |
Output fuse | 10 A gL/gG (N/O contact) |
6 A gL/gG (N/C contact) |