Key Commercial Data
Orderkey | 2700577 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 284 (C-6-2017) |
GTIN | 4046356916417 |
Weight per Piece (excluding packing) | 189.100 g |
Custom tariff number | 85364900 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -40 °C … 70 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % (A1/A2) |
---|---|
20.4 V DC … 26.4 V DC | |
Rated control supply current IS | typ. 50 mA |
Power consumption at US | typ. 1.2 W |
Inrush current | typ. 400 mA (Δt s) |
Filter time | max. 2 ms (at A1-A2; test pulse width) |
≥ 100 ms (at A1-A2; test pulse rate) | |
Diagnostic supply voltage UD | 24 V DC -15 % / +10 % (31/A2, TBUS) |
Input current at UD | 6 mA (at 31-A2 for UD; depending on load + 100 mA at M1 and 32) |
Inrush current at UD | typ. 2.5 A (Δt D) |
Protective circuit | Serial protection against polarity reversal 33 V suppressor diode (A1/A2)33 V suppressor diode (31/A2) |
Relay outputs: enabling current path
Output name | Enabling current path |
---|---|
Output description | 2 N/O contacts in series, without delay, floating |
Number of outputs | 1 (safety-related N/O contacts: 13/14 (13F/14)) |
Contact type | 1 enabling current path |
Contact material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Limiting continuous current | 6 A (13/14 for high-demand) |
4 A (13F/14 with high/low demand, 13/14 with low demand) | |
Inrush current | min. 3 mA |
max. 6 A (N/O contact 13/14) | |
4 A (N/O contact 13F/14) | |
Sq. Total current | 36 A2(13/14, see to derating) |
16 A2(13F/14, see to derating) | |
Switching capacity | min. 60 mW |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 10x 106cycles |
Switching capacity according to IEC 60947-5-1 | 4 A (24 V (DC13); N/O contact 13/14) |
5 A (250 V (AC15); N/O contact 13/14) | |
4 A (250 V (AC15); N/O contact 13F/14) | |
Output fuse | 6 A gL/gG (N/O contact 13/14) |
4 A gL/gG (for low-demand applications) |