Key Commercial Data
Orderkey | 1009832 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 223 (C-6-2019) |
GTIN | 4055626482712 |
Weight per Piece (excluding packing) | 180.000 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C … 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 70 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
Designation | A1/A2 |
---|---|
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % (provide external protection) |
Rated control supply current IS | typ. 75 mA |
Power consumption at US | typ. 1.8 W |
Inrush current | < 4 A (Δt = 3 ms at Us) |
Filter time | 20 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal Suppressor diode |
Digital inputs
Input name | Sensor circuit |
---|---|
S10, S12, S13, S22 | |
Description of the input | safety-related sensor inputs |
NPN (S10, S12, S13), PNP (S22) | |
Number of inputs | 4 |
Input voltage range “1” signal | 20.4 V DC … 26.4 V DC |
Inrush current | < 40 mA (typ. with USat S10) |
< 300 mA (typ. with USat S12, Δt = 150 ms) | |
< 3 mA (Typically with USat S13) | |
> -300 mA (Typically with USat S22, Δt = 150 ms) | |
Current consumption | 40 mA (typ. with USat S10) |
45 mA (Typically with USat S12) | |
3 mA (Typically with USat S13) | |
-35 mA (Typically with USat S22, Δt = 150 ms) | |
Filter time | 2 ms (At S10, S12, S13; test pulse width of low test pulses) |
1 ms (At S10, S12, S13; test pulse rate of low test pulses) | |
No brightness test pulses / high test pulses permitted. | |
Max. permissible overall conductor resistance | 50 Ω |
Concurrence input 1/2 | ∞ |
Protective circuit/component | Suppressor diode |
Input name | Start circuit |
Y1, S34, S35 | |
Description of the input | non-safety-related |
NPN | |
Input voltage range “1” signal | 20.4 V DC … 26.4 V DC |
Inrush current | < 60 mA (Typically with USat Y1, Δt = 150 ms) |
< 270 mA (Typically with USat S34, Δt = 15 ms) | |
< 80 mA (Typically with USat S35, Δt = 25 ms) | |
Current consumption | typ. 10 mA (Typically with USat Y1) |
typ. 34 µA (Typically with USat S35) | |
Max. permissible overall conductor resistance | 50 Ω |
Protective circuit/component | Suppressor diode |
Relay outputs: enabling current path
Output name | Enabling current path |
---|---|
13/14, 23/24 | |
Output description | safety-related N/O contacts |
2 NO contacts each in series, without delay, floating | |
Number of outputs | 2 (undelayed) |
Contact type | 2 enabling current paths |
Contact material | AgSnO2 |
Switching voltage | min. 10 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Limiting continuous current | 6 A |
Inrush current | min. 10 mA |
max. 6 A | |
Sq. Total current | 72 A2(observe derating) |
Switching capacity | min. 100 mW |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 10x 106cycles |
Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
5 A (250 V (AC15)) | |
Output fuse | 10 A gL/gG |
4 A gL/gG (for low-demand applications) |
Alarm outputs
Designation | Y30 |
---|---|
Output description | PNP |
non-safety-related | |
Number of outputs | 1 |
Voltage | approx. 23.9 V DC (Us– 0.1 V) |
Current | max. 100 mA |
Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
Protective circuit/component | Suppressor diode |
Times
Typical pickup time at US | 200 ms (when controlled via A1) |
---|---|
Typical response time at US | 200 ms (automatic start) |
30 ms (manual, monitored start) | |
Typical release time at US | 25 ms (when actuation is via the sensor circuit) |
60 ms (when controlled via A1) | |
Restart time | < 1 s (Boot time) |
Recovery time | < 500 ms |
General
Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 169.38 g |
Mounting position | vertical or horizontal |
Mounting type | DIN rail mounting |
Assembly instructions | See derating curve |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Housing material | PBT |
Housing color | yellow |
Operating voltage display | 1 x green LED |
Status display | 4 x green LEDs |
Connection data
Connection method | Push-in connection |
---|---|
pluggable | no |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Safety-related characteristic data
Stop category | 0 |
---|---|
Designation | IEC 61508 – High demand |
Safety Integrity Level (SIL) | 3 |
Designation | IEC 61508 – Low demand |
Safety Integrity Level (SIL) | 3 |
Designation | EN ISO 13849 |
Performance level (PL) | e |
Category | 4 (5 A DC13; 5 A AC15; 8760 switching cycles/year) |
Designation | EN 62061 |
Safety Integrity Level Claim Limit (SIL CL) | 3 |
Standards and Regulations
Designation | Air clearances and creepage distances between the power circuits |
---|---|
Standards/regulations | DIN EN 50178 |
Rated insulation voltage | 250 V |
250 V | |
Degree of pollution | 2 |
Overvoltage category | III |
Shock | 15g |
Vibration (operation) | 10 Hz … 150 Hz, 2g |
Conformance | CE-compliant |