Key Commercial Data
Orderkey | 2700540 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 254 (C-6-2017) |
GTIN | 4046356912716 |
Weight per Piece (excluding packing) | 141.220 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -40 °C … 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
---|---|
20.4 V DC … 26.4 V DC | |
Rated control supply current IS | typ. 84 mA |
Power consumption at US | typ. 2 W |
Inrush current | 5 A (Δt = 200 µs at Us) |
Filter time | 1 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Surge protection Suppressor diode |
Protection against polarity reversal for rated control circuit supply voltage |
Digital inputs
Input voltage range “0” signal | 0 V DC … 5 V DC (for safe Off; at S12) |
---|---|
Input current range “0” signal | 0 mA … 2 mA (for safe Off; at S12) |
Inrush current | < 20 mA (with Us/Ixto S12) |
< 200 mA (with Us/Ixto S34) | |
< 5 mA (with Us/Ixto S22) | |
> -15 mA (with Us/Ixto S22/0V) | |
Current consumption | < 5 mA (with Us/Ixto S12) |
< 5 mA (with Us/Ixto S22) | |
> -5 mA (with Us/Ixto S34) | |
> -5 mA (with Us/Ixto S22/0V) | |
< 10 mA (with Us/Ixto S34) | |
Filter time | max. 1.5 ms (at S12, S22; test pulse width) |
min. 7.5 ms (at S12, S22; test pulse rate) | |
Test pulse rate = 5 x Test pulse width | |
Voltage at input/start and feedback circuit | 24 V DC -15 % / +10 % |
Max. permissible overall conductor resistance | 150 Ω |