Key Commercial Data
| Orderkey | 1015503 |
|---|---|
| Packing unit | 1 |
| GTIN | 4055626496467 |
| Custom tariff number | 85371098 |
Note
| Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C … 70 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 70 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
| Designation | A1/A2 |
|---|---|
| Rated control circuit supply voltage US | 24 V DC -20 % / +25 % (provide external protection) |
| Rated control supply current IS | typ. 54 mA (No load) |
| Power consumption at US | typ. 1.3 W |
| Inrush current | < 5 A (Δt = 200 µs at Us) |
| Filter time | 1 ms (For the logic. At A1 in the event of voltage dips at Us) |
| Protective circuit | Parallel protection against polarity reversal Suppressor diode Provide external protection, see safety notes. Fuse type: 5 A FF |
Digital inputs
| Input name | Sensor circuit |
|---|---|
| S10, S12, S22 | |
| Description of the input | safety-related sensor inputs |
| NPN, IEC 61131-2 type 3 (S10, S12) PNP (S22) |
|
| Number of inputs | 3 |
| Input voltage range “0” signal | 0 V DC … 5 V DC (S10, S12) |
| S22 open | |
| Input voltage range “1” signal | 11 V DC … 30 V DC (S10, S12) |
| 0 V … 0 V (S22) | |
| Input current range “0” signal | 0 mA … 2 mA (S10, S12) |
| Inrush current | < 10 mA (Typically with USat S10/S12, Δt = 500 µs) |
| > -5 mA (typ. with USat S22, Δt = 500 µs) | |
| Current consumption | 4 mA (S10, S12) |
| -4 mA (S22) | |
| Filter time | max. 1.5 ms (Test pulse width of low test pulses) |
| Test pulse rate = 5 x Test pulse width | |
| Does not apply for S22 | |
| Deactivate switch-on pulses/light tests for safety applications. | |
| Max. permissible overall conductor resistance | 150 Ω |
| Concurrence input 1/2 | ∞ |
| Protective circuit/component | Suppressor diode |
| Input name | Start circuit |
| S34, S35 | |
| Description of the input | non-safety-related |
| NPN | |
| Number of inputs | 2 |
| Input voltage range “1” signal | 19.2 V DC … 30 V DC |
| Inrush current | < 10 mA (Typically with US, Δt |
| Current consumption | < 7 mA (Typically with USat S34) |
| < 5 mA (Typically with USat S35) | |
| Max. permissible overall conductor resistance | 150 Ω |
| Protective circuit/component | Suppressor diode |
| Input name | External release |
| S36 | |
| Description of the input | safety-related |
| NPN, IEC 61131-2, type 3 | |
| Number of inputs | 1 |
| Input voltage range “0” signal | 0 V DC … 5 V DC |
| Input voltage range “1” signal | 11 V DC … 30 V DC |
| Current consumption | 7 mA |
| Protective circuit/component | Suppressor diode |
Digital outputs
| Output name | 14, 24 |
|---|---|
| Output description | Safety-related digital outputs |
| PNP, IEC 61131-2 Type 2 | |
| Number of outputs | 2 |
| Output voltage | ≥ 23 V DC (Us– 1 V) |
| Output current | max. 2.4 A |
| Inrush current | max. 4.8 A (Δt = 10 ms) |
| Output voltage when switched off | < 5 V DC (in the safe state) |
| Leakage current | max. 1 mA (in the safe state) |
| Ohmic load | min. 12 Ω |
| Max. capacitive load | max. 10 µF (2.4 A load) |
| max. 4.7 µF (1 A load) | |
| Max. inductive load | max. 1 H |
| Min. load current | 2 mA |
| Switching frequency | 1 Hz (Resistive, inductive, capacitive) |
| Type of protection | Freewheeling circuit for inductive loads |
| Limitation of the voltage induced on circuit interruption | max. 50 V |
Alarm outputs
| Designation | M1 |
|---|---|
| Output description | PNP |
| non-safety-related | |
| Number of outputs | 1 |
| Voltage | approx. 22 V DC (Us– 2 V) |
| Current | max. 100 mA |
| Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
| Protective circuit/component | Suppressor diode |
| Short-circuit protection | Yes |
Times
| Typical pickup time at US | < 200 ms (with Uswhen controlled via A1) |
|---|---|
| Typical response time at US | < 200 ms (automatic start) |
| < 175 ms (manual, monitored start) | |
| Response time | < 10 ms (Take the extension of the response time into consideration if you switch several devices in sequence.) |
| Restart time | < 250 ms (Boot time) |
| Recovery time | 250 ms (following demand of the safety function) |
General
| Nominal operating mode | 100% operating factor |
|---|---|
| Net weight | 104.382 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
| Operating voltage display | 1 x green LED |
| Status display | 3 x green LED |
| Indication | 1 x red LED |
Connection capacity
| Connection method | Push-in spring connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid | 0.2 mm² … 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² … 1.5 mm² |
| Conductor cross section AWG / kcmil | 24 … 16 |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² … 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² … 1.5 mm² (only together with CRIMPFOX 6) |
| Stripping length | 8 mm |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 – High demand |
| Safety Integrity Level (SIL) | 3 |
| Designation | EN ISO 13849 |
| Performance level (PL) | e |
| Category | 4 |
| Designation | EN 62061 |
| Safety Integrity Level Claim Limit (SIL CL) | 3 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178, EN 60947-5-1 |
| Rated insulation voltage | 50 V |
| 50 V AC | |
| Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 30g |
| Vibration (operation) | 10 Hz … 150 Hz, 5g |
| Conformance | CE-compliant |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |