Key Commercial Data
Orderkey | 2708863 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 318 (C-6-2017) |
GTIN | 4046356078993 |
Weight per Piece (excluding packing) | 212.400 g |
Custom tariff number | 85176200 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Permissible humidity (operation) | 30 % … 95 % (non-condensing) |
Altitude | ≤ 5000 m (For restrictions see manufacturer’s declaration) |
≤ 2000 m (When used in EX zone 2) | |
Degree of protection | IP20 |
Noise immunity | EN 61000-4-2 |
General
Transmission channels | 2 (1/1), TD, RD, half duplex |
---|---|
Bit delay | 1 bit (Direct mode) |
Bit distortion, input | max. ± 35 % |
Bit distortion, output | < 6.25 % |
Electrical isolation | VCC // TBUS // PROFIBUS (A) // PROFIBUS (B) |
Test voltage data interfaces | 1.5 kV |
Test voltage data interface/power supply | 1.5 kVrms(50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 |
Net weight | 212.4 g |
Housing material | PA 6.6-FR |
Color | green |
MTBF | 1136 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
238 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
MTTF | 1638 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
812 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) | |
340 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA nC IIC T4 Gc X (Please follow the special installation instructions in the documentation!) |
UL, USA/Canada | cULus listed UL 508 |
Class I, Zone 2, AEx nA nC IIC T6 | |
Class I, Zone 2, Ex nA nC IIC T6 Gc X | |
Class I, Div. 2, Groups A, B, C, D |
Power supply
Nominal supply voltage | 24 V DC (With UL approval) |
---|---|
Supply voltage range | 18 V DC … 30 V DC (via pluggable COMBICON screw terminal block) |
Typical current consumption | < 90 mA (24 V DC) |