Key Commercial Data
Orderkey | 2906492 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
GTIN | 4055626082059 |
Weight per Piece (excluding packing) | 21.760 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
General
EN type | T3 |
---|---|
Number of ports | One |
Mode of protection | L-N |
L-PE | |
N-PE | |
(L+) – (L-) | |
(L+/L-) – PE | |
Mounting type | on base element |
Color | jet black RAL 9005 |
Housing material | PA 6.6 |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | Male |
Number of positions | 2 |
Surge protection fault message | optical |
Additional descriptions
Note | PLT-T3-24-P must not be used in DC applications with grounded positive pole. |
---|
Protective circuit
Nominal voltage UN | 24 V AC (TN-S) |
---|---|
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 34 V AC |
44 V DC | |
Rated load current IL | 16 A AC (at 63 °C) |
10 A DC | |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In(8/20) µs | 1 kA |
Standby power consumption PC | ≤ 60 mVA |
Reference test voltage UREF | 27 V AC |
Combination wave UOC | 2 kV |
Voltage protection level Up(L-N) | ≤ 0.18 kV |
Voltage protection level Up(L-PE) | ≤ 0.55 kV |
Voltage protection level Up(N-PE) | ≤ 0.55 kV |
TOV behavior at UT(L-N) | 36 V AC (5 s / withstand mode) |
TOV behavior at UT(L-PE) | 42 V AC (5 s / withstand mode) |
Response time tA(L-N) | ≤ 25 ns |
Response time tA(L-PE) | ≤ 100 ns |
Response time tA(N-PE) | ≤ 100 ns |
Short-circuit current rating ISCCR | 1.5 kA AC |
1 kA DC | |
Max. backup fuse with branch wiring | 16 A AC (B) |
10 A DC (gG / B) | |
Maximum backup fuse for through wiring | 16 A AC (B) |
10 A DC (gG / B) |