Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
General
EN type | T3 |
---|---|
Number of ports | One |
Mode of protection | L-N |
L-PE | |
N-PE | |
Mounting type | on base element |
Color | jet black RAL 9005 |
Housing material | PA 6.6 |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | Male |
Number of positions | 2 |
Surge protection fault message | optical |
Protective circuit
Nominal voltage UN | 230 V AC (TN-S) |
---|---|
230 V AC (TT – only in use with RCD) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 255 V AC |
Rated load current IL | 16 A AC (at 63 °C) |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In (8/20) µs | 3 kA |
Standby power consumption PC | ≤ 350 mVA |
Reference test voltage UREF | 255 V AC |
Combination wave UOC | 6 kV |
Voltage protection level Up (L-N) | ≤ 1.25 kV |
Voltage protection level Up (L-PE) | ≤ 1.4 kV |
Voltage protection level Up (N-PE) | ≤ 1.4 kV |
TOV behavior at UT (L-N) | 440 V AC (5 s / withstand mode) |
440 V AC (120 min / withstand mode) | |
TOV behavior at UT (L-PE) | 440 V AC (5 s / withstand mode) |
440 V AC (120 min / withstand mode) | |
1455 V AC (200 ms / safe failure mode) | |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / safe failure mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Short-circuit current rating ISCCR | 1.5 kA AC |
Max. backup fuse with branch wiring | 16 A (B) |
Maximum backup fuse for through wiring | 16 A (B) |
UL specifications
SPD Type | 4CA |
---|---|
Maximum continuous operating voltage MCOV | 255 V AC |
Mode of protection | L-N |
L-G | |
N-G | |
Power distribution system | Single phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 1500 V |
Measured limiting voltage MLV (L-G) | 1200 V |
Measured limiting voltage MLV (N-G) | 1200 V |
Nominal discharge current In | 3 kA |