Key Commercial Data
Orderkey | 1090867 |
---|---|
Packing unit | 1 pc |
GTIN | 4055626901381 |
Weight per Piece (excluding packing) | 0.000 g |
Custom tariff number | 85366990 |
Country of origin | DE (Germany) |
Note
Note | Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. |
---|---|
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules | |
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. | |
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
Ambient conditions
Ambient temperature (operation) | -40 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Maximum altitude | ≤ 2000 m |
Degree of protection | IP20 |
≥ IP54 (Installation location) |
Input data
Nominal input voltage UN | 12 V DC |
---|---|
Protective circuit | Damping diode |
Polarity protection diode |
Output data
Compatible components | Miniature relay, 2904475 REL-MR- 12DC/1IC, 1081616 REL-MR- 12DC/1ICT |
---|
General
Color | gray |
---|---|
Operating mode | 100% operating factor |
Mounting position | any |
Assembly instructions | In rows with zero spacing |
Test voltage relay winding/relay contact | 4 kVrms(50 Hz, 1 min.) |
Connection data
Connection name | Input side |
---|---|
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.14 mm² … 2.5 mm² |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
0.2 mm² … 2.5 mm² (Single ferrule) | |
2x 0.5 mm² … 1.5 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 … 14 |
Connection data 2
Connection name | Output side |
---|---|
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.14 mm² … 2.5 mm² |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
0.2 mm² … 2.5 mm² (Single ferrule) | |
2x 0.5 mm² … 1.5 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 … 14 |
Standards and Regulations
Standards/regulations | EN 50178 |
---|---|
EN 61810-1 | |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 6 kV |
Insulation | Safe isolation, reinforced insulation |
Pollution degree | 2 |
Overvoltage category | III |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |