Key Commercial Data
Orderkey | 2904921 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 236 (C-5-2017) |
GTIN | 4046356900966 |
Weight per Piece (excluding packing) | 416.700 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Measuring transducer supply
Nominal supply voltage | 24 V DC -20 % … +25 % |
---|---|
Nominal supply voltage range | 19.2 V DC … 30 V DC |
Max. current consumption | 190 mA |
Power consumption | 4 W |
Measuring coil input data
Frequency measuring range | 40 Hz … 20000 Hz |
---|---|
Position error | < 1 % |
Linearity error | 0.1 % |
Measuring transducer input data
Measuring ranges (current) | 100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A |
---|---|
Configurable/programmable | Via DIP switches |
Phase angle | < 1 ° |
Rated power | 1.5 VA |
Max. distances for copper cables at PN max | 32 m (0.75 mm² (AWG 20)) |
64 m (1.5 mm² (AWG 16)) | |
107 m (2.5 mm² (AWG 14)) |
Measuring transducer signal input
Input signal (at 50 Hz) | 100 mV (1000 A) |
---|---|
Input impedance | 27 kΩ (smallest measuring range) |
Measuring coil signal output
Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
---|---|
Output voltage (in no-load operation) | VOUT= M * dI/dt |
Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT= 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |