Key Commercial Data
Orderkey | 2982126 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 310 (C-5-2017) |
GTIN | 4017918989767 |
Weight per Piece (excluding packing) | 10.730 g |
Custom tariff number | 85364190 |
Country of origin | HU (Hungary) |
Ambient conditions
Ambient temperature (operation) | -25 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -25 °C … 70 °C |
Input data
Nominal input voltage UN | 60 V DC |
---|---|
Input voltage range in reference to UN | 0.9 … 1.1 |
Input voltage range | 54 V DC … 66 V DC |
Switching threshold “0” signal, voltage | ≤ 20 V DC |
Switching threshold “1” signal voltage | ≥ 35 V DC |
Typical input current at UN | 3 mA |
Typical response time | 25 µs |
Typical turn-off time | 400 µs |
Type of protection | Reverse polarity protection |
Protective circuit/component | Polarity protection diode |
Transmission frequency | 300 Hz |
Power dissipation for nominal condition | 0.18 W |
Output data
Output nominal voltage | 24 V DC |
---|---|
Output voltage range | 3 V DC … 33 V DC |
Limiting continuous current | 5 A (see derating curve) |
Maximum inrush current | 15 A (10 ms) |
Surge voltage protection | > 33 V DC |
Voltage drop at max. limiting continuous current | ≤ 200 mV |
Output circuit | 2-wire, floating |
Type of protection | Reverse polarity protection |
Surge protection | |
Protective circuit/component | Polarity protection diode |
General
Test voltage input/output | 2.5 kV (50 Hz, 1 min.) |
---|---|
Mounting position | any |
Assembly instructions | In rows with zero spacing |
Operating mode | 100% operating factor |
Degree of protection | RT III (wash-proof) |
Flammability rating according to UL 94 | V0 |
Designation | Standards/regulations |
Standards/regulations | IEC 60664 |
EN 50178 | |
Degree of pollution | 2 |
Overvoltage category | III |