Key Commercial Data
Orderkey | 2982171 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Catalog page | Page 311 (C-5-2017) |
GTIN | 4017918996970 |
Weight per Piece (excluding packing) | 10.330 g |
Custom tariff number | 85364190 |
Country of origin | HU (Hungary) |
Ambient conditions
Ambient temperature (operation) | -25 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -25 °C … 70 °C |
Input data
Nominal input voltage UN | 24 V DC |
---|---|
Input voltage range in reference to UN | 0.8 … 1.2 |
Input voltage range | 19.2 V DC … 28.8 V DC |
Switching threshold “0” signal, voltage | < 8.4 V DC |
Switching threshold “1” signal voltage | > 18 V DC |
Typical input current at UN | 7 mA |
Typical response time | 10 ms |
Typical turn-off time | 10 ms |
Type of protection | Reverse polarity protection |
Protective circuit/component | Polarity protection diode |
Transmission frequency | 10 Hz |
Power dissipation for nominal condition | 0.17 W |
Output data
Output nominal voltage | 230 V AC |
---|---|
Output voltage range | 24 V AC … 253 V AC |
Limiting continuous current | 2 A (see derating curve) |
Maximum inrush current | 30 A (10 ms) |
Min. load current | 25 mA |
Leakage current | typ. 1 mA |
Surge current | 30 A (10 ms) |
Max. load value | 4 A2s (tp = 10 ms, at 25 °C) |
Voltage drop at max. limiting continuous current | ≤ 1 V |
Output circuit | 2-conductor floating, zero voltage switch |
Type of protection | Surge protection |
Protective circuit/component | RC element |
General
Test voltage input/output | 2.5 kV (50 Hz, 1 min.) |
---|---|
Mounting position | any |
Assembly instructions | See derating curve |
Operating mode | 100% operating factor |
Degree of protection | RT III (wash-proof) |
Flammability rating according to UL 94 | V0 |
Designation | Standards/regulations |
Standards/regulations | IEC 60664 |
EN 50178 | |
Degree of pollution | 2 |
Overvoltage category | III |