Key Commercial Data
| Orderkey | 2765699 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 109 (TT-2009) |
| GTIN | 4017918066543 |
| Weight per Piece (excluding packing) | 31.450 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Number of positions | 2 |
| Direction of action | Line-Line |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 6 A |
| Operating effective current ICat UC | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-line) | 1.5 kA |
| Total discharge current Itotal(8/20) µs | 1.5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 1.5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 185 A |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 55 V |
| Residual voltage at In(line-line) | ≤ 95 V |
| Response time tA(line-line) | ≤ 1 ns |
| Input attenuation aE, asym. | |
| Capacity (line-line) | typ. 7 nF |
| Surge protection fault message | none |
| Impulse durability (line-line) | C1 – 1 kV/500 A |
| C2 – 2 kV / 1 kA | |
| C3 – 100 A |
Connection data
| Connection method | Screw terminal blocks |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm … 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
| Conductor cross section solid | 0.2 mm² … 4 mm² |
| Conductor cross section AWG | 24 … 12 |