Key Commercial Data
| Orderkey | 2924061 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 152 (C-5-2017) |
| GTIN | 4046356337359 |
| Weight per Piece (excluding packing) | 137.900 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C … 60 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % … 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 EN 61326 |
Input data
| Non-load voltage | ~ 8 V DC |
|---|---|
| Switching points (attenuated) | < 1.2 mA (blocking) |
| Switching points (unattenuated) | > 2.1 mA (conductive) |
| Signal input | Intrinsically safe |
| Available input sources | NAMUR proximity sensors (EN 60947-5-6) |
| Short-circuit current | ~ 8 mA |
| Switching hysteresis | < 0.2 mA |
| Line fault detection | Break 0.05 mA < IIN < 0.35 mA |
| Short circuit 100 Ω < RSensor < 360 Ω |
Output data
| Switching output | Relay output |
|---|---|
| Contact type | 2 N/O contacts |
| Contact material | AgSnO2, hard gold-plated |
| Maximum switching voltage | 250 V AC (2 A) |
| 120 V DC (0.2 A) | |
| 30 V DC (2 A) | |
| Maximum switching capacity | 500 VA |
| Mechanical service life | 107cycles |
| Switching frequency | ≤ 20 Hz (without load) |