Key Commercial Data
Orderkey | 2804649 |
---|---|
Packing unit | 10 pc |
Catalog page | Page 117 (C-4-2017) |
GTIN | 4046356428286 |
Weight per Piece (excluding packing) | 63.740 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -40 °C … 80 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
General
Housing material | PBT |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | anthracite grey RAL 7016 |
Mounting type | DIN rail: 35 mm |
Type | DIN rail module, one-piece |
Direction of action | Line-Earth Ground |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 36 V DC |
25 V AC | |
Rated current | 350 mA (40° C) |
Operating effective current ICat UC | ≤ 2 µA |
Residual current IPE | ≤ 8 µA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Pulse discharge current Iimp(10/350) µs (line-earth) | 500 A |
2 kA (in total) | |
Total discharge current Itotal(8/20) µs | 20 kA |
Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
20 kA (in total) | |
Nominal pulse current Ian (10/1000) µs (line-earth) | 50 A |
200 A (in total) | |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 60 V |
Residual voltage at In(line-earth) | ≤ 50 V |
Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 60 V |
Voltage protection level Up(line-earth) | ≤ 60 V (C1 – 500 V / 250 A) |
≤ 95 V (C2 – 10 kV / 5 kA) | |
≤ 55 V (C3 – 10 A) | |
≤ 55 V (C3 – 50 A) | |
≤ 250 V (D1 – 500 A) | |
Response time tA(line-earth) | ≤ 1 ns |
Input attenuation aE, asym. | typ. 0.3 dB (1 MHz / 50 Ω) |
typ. 0.2 dB (350 kHz / 150 Ω) | |
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system | typ. 6 MHz |
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 2 MHz |
Capacity | ≤ 1.3 nF (per channel) |
Resistance in series | 3.3 Ω ±20 % |
Surge protection fault message | none |
Max. required back-up fuse | 315 mA (T) |
Impulse durability (line-earth) | C1 – 500 V / 250 A |
C2 – 10 kV/5 kA | |
C3 – 50 A | |
D1 – 500 A | |
Alternating current carrying capacity (line-earth) | 5 A – 1 s |
Connection data
Connection method | Screw connection |
---|---|
Screw thread | M3 |
Tightening torque | 0.8 Nm |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 14 |