Ambient conditions
| Ambient temperature (operation) | -25 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 85 °C |
| Permissible humidity (operation) | 75 % … 85 % (in the range of -25°C … +55°C, appropriate measures against increased humidity (> 85%) must be taken.) |
| Permissible humidity (storage/transport) | 75 % … 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.) |
| Air pressure (operation) | 80 kPa … 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa … 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Interfaces
| Designation | INTERBUS |
|---|---|
| No. of channels | 2 |
| Connection method | Inline shield connector |
| Transmission speed | 500 kbps |
| Transmission physics | Copper |
| Designation | Inline local bus |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
System limits of the bus coupler
| Number of local bus devices that can be connected | 63 |
|---|---|
| Number of devices with parameter channel | 62 |