Ambient conditions
| Ambient temperature (operation) | -25 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 85 °C |
| Permissible humidity (operation) | 10 % … 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % … 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa … 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa … 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 190 g |
| Note on weight specifications | with connectors |
| Operating mode | Process data mode with 5 words/1 word PCP |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Failure of or insufficient communications power UL I/O error message sent to the bus coupler | |
| User error Error message in the process data |
Interfaces
| Designation | Inline local bus |
|---|---|
| Connection method | Inline data jumper |
| Transmission speed | 2 Mbps |
| Transmission physics | Copper |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 115 mA |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC … 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 6 mA |
| Power consumption | typ. 1.01 W (entire device) |