Key Commercial Data
Orderkey | 2703198 |
---|---|
Packing unit | 50 pc |
GTIN | 4017918061098 |
Weight per Piece (excluding packing) | 42.300 g |
Custom tariff number | 85369010 |
Country of origin | PL (Poland) |
General
Number of positions | 6 |
---|---|
Number of levels | 1 |
Number of connections | 12 |
Potentials | 6 |
Nominal cross section | 4 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 1.02 W |
Ambient temperature (operation) | -40 °C … 80 °C |
Maximum load current | 32 A (with 4 mm² conductor cross section) |
Nominal current IN | 30 A |
Nominal voltage UN | 275 V |
Open side panel | No |
Terminal block mounting | When attaching the product to the mounting surface, please ensure that the housing is not damaged when tightening the center screw |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Connection data
Connection method | Screw connection |
---|---|
Connection in acc. with standard | IEC 60947-7-1/IEC 60998 |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Min. AWG conductor cross section, flexible | 24 |
Max. AWG conductor cross section, flexible | 12 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
2 conductors with same cross section, solid min. | 0.2 mm² |
2 conductors with same cross section, solid max. | 1.5 mm² |
2 conductors with same cross section, stranded min. | 0.2 mm² |
2 conductors with same cross section, stranded max. | 1.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 1 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.25 mm² |
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 1.5 mm² |
Stripping length | 8 mm |
Internal cylindrical gage | A3 |
Screw thread | M3 |
Tightening torque, min | 0.6 Nm |
Tightening torque max | 0.8 Nm |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-1/IEC 60998 |
---|---|
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |